37 of 1925 - Relating to oil burning equipment ROLL CALL
VOTING AYE NAY
Barnes Salt Lake City,Utah, = ,192
Burton
Finch I move that the ordinance be passed.
CGTee
reen
Mr. Chairman
Result AN ORDINANCE
An Ordinance amending Sections 1120, 1123, 1127
of Chapter XXIII of the Revised Ordinances of Salt Lake
City, 1920, relating to Explosives and Combustibles.
Be it ordained by the Board of Commissioners of
Salt Lake City, Utah:
Section 1. That Section 1120, 1123, 1127 of
Chapter XXIII of the Revised Ordinances of Salt Lake City,
1920, relatirg to Explosives and Combustibles be and the
same are hereby amended. to read as follows:-
SECTION 1120. FLASH TEST, DEFINED. For the pur-
pose of this ordinance, "Standard Flash Test" means "Will
not flash or emit an inflamable vapor at a temperature lower
than one hundred and thirty (130) degrees Fahrenheit".
SECTION 1123. FLASH TEST 130 DEGREES OR HIGHER.
(a) Quantity under 500 gallons. Kerosene, coal oil, pet-
roleum, distillate, products of petroleum, or hydro-carbon
liquids of standard flash test, in quantities not exceeding •
five hundred (500) gallons, may be kept or stored in metallic
cans or metallio tanks of not exceeding sixty (60) gallon
capacity, or in an underground tank as speoified.
(b) Quantity over 500 gallons. It shall be unlawful to
keep or store, or permit to be kept or stored in any building,
or upon any premises, street, or place, in quantities in excess
of five hundred (600) gallons, any petroleum, distillate, pro-
ducts of petroleum or hydro-carbon liquids of standard flash
test; except in tanks, or in barrels or metallic cans in a one-
story brick, stone, or concrete building, with a concrete or
hollow tile roof, with no interior woodwork whatever, with all
exterior openings protected with wire glass not less than one-
quarter (1/4) inch thick in metal frames and sash, or with wood-
en tin-clad doors or shutters. All door openings to have masonry
sills rising not less than one foot above the floor. Such
buildings to be occupied exclusively for storage of oils and
liquids.
SECTION 11270 OIL BURNING EQUIPMENTS, AND DOMESTIC
OIL BURNING EQUIPMENT.
(a) OIL BURNING EQUIPMENTS. Oil burning equipments are those
using only liquids having flash point above 1500F., closed cup
tester. Oil burning equipments shall be operated only when a
competent attendant is constantly on the premises. An oil burn-
ing system shall consist of all equipment connected to the burn-
er and located within the building, including auxiliary supply
tanks and provisions for filling same, piping, burner, and all
-2-
accessories. Only systems approved by the Chief of the Fire
Department shall be used.
(b) STORAGE TANKS FOR OIL BURNING EQUIPMENTS. Storage tanks
shall be placed underground, provided that above ground tanks of
not to exceed 1000 gallon capacity may be used when approved by
the Chief of the Fire Department.
1 - UNDERGROUND TANKS. Underground tanks shall be con-
structed of galvanized steel, basic open hearth steel or wrought
iron of a minimum gauge ( U.S. Standard) depending upon the capa-
city, as given in the following table:-
Minimum
Capacity ( Gallons) Thickness of Material
• 1 to 560 14 gauge
561 to 1,100 12 gauge
1,101 to 4,000 7 gauge
4,001 to 10,500 .. 1/4 inch
10,501 to 20,000 5/16 inch
20,001 to 30,000 3/8 inch
All joints shall be riveted and caulked, brazed, welded or made
by some equally satisfactory process. Tanks shall be tight mad
sufficiently strong to bear without injury the most severe strain
to which they may be subjected in practice. Shells of tanks shall !
be properly reinforced Where connections are made, and all con-
nections made through the top of tank above the liquid level. All
tanks shall be thoroughly coated on the outsislewith tar, asphalt
or other suitable rust-resisting material, dependent upon the
condition of soil in which they are placed. Where soil is impreg-
nated with corrosive materials, tanks shall also be made of heav-
ier metal. An independent, permanently open galvanized iron vent
pipe terminating outside of building shall be provided for every
tank. The lower end of the vent pipe shall not extend through the
stop into the tank for a distance of more than one inch. Vent op-
enings shall be screened (40x40 non-corrodible wire mesh or its
equivalent, preferably cone-shape and shall be of sufficient
area to permit proper inflow of 1 quid during the filling opera-
tion arri in no case less than 1 inch in diameter. Screens shall
be accessible for examination and removal. Vent pipes shall be
provided with weather-proof hoods, and terminate twelve feet abov=
top to fill-pipe, or, if tight connection is made in filling line,
to a point one foot above the level of the top of the highest
reservoir from which the tanks may be filled, and preferably not
less than three feet, measured horizontally and vertically, from
any window or other building opening. End of filling pipe in tank
shall be turned up so as to form a trap or seal, and when install-
ed in the vicinity of any door or other building opening shall be
as remote therefrom as possible so as to prevent liability of
flow of oil through building openings; terminal shall be outside
of building in a tight, incombustible box of casting, so designed
as to make access difficult by unauthorized persons. Manhole cover=
shall be securely fastened in order to make access difficult by
unauthorized persons. No manhole shall be used for filling purpose..
Tanks shall be buried underground with top of the tanks not less
than three feet below the surface of the ground, and below the
level of any piping to which the tanks may be connected, except
that in lieu of the three feet cover, tanks may be buried under
18 inches of earth and a cover of reinforced concrete at least 6
inches in thickness provided, which shall extend at least one b of
eyond the outline of tank in all directions; concrete slab to be
set on a firm well-tamped earth foundation. Tanks shall be securely
nohored or weighted in placd to prevent floating. Where a tank
cannot be entirely buried, it shall be covered with earth to a
epth of at least 3 feet and sloped on all sides, slopes not to be
11
1 -3-
less than 3 to 1. Such cases shall also be subject to such other
requirements as may be deemed necessary by the Chief of the Fire
Department. If tank cannot be set below the level of all piping
Ito which it is connected, satisfactory arrangements shall be pro-
Ivided to prevent siphoning or gravity flow in case of accident to
'the piping. Tanks shall be set on a firm foundation and surround-
ed. with soft earth or sand well tamped in place. When located un-
derneath a building, the tanks shall be buried with top of tanks
not less than 2 feet below the level of the floor. The floor im-
Imediately above the tanks shall be of reinforced concrete at least
119 inches in thickness, or some other type of construction of equi-,
fralent strength and fire resistance, extending at least one foot
beyond the outline of the tanks in all directions, and provided
with ample means of support independent of any tank.
2 - ABOVE GROUND TANKS. Above ground tanks including top
shall be constructed of basic open hearth steel or wrought iron of
Is minimum gauge ( U.S. Standard) as specified in the following
table:-
Minimum
Capacity ( Gallons ) Thickness of Material
1 to 30 18 gauge
31 to 350 16 gauge
351 to 1000 14 gauge
,Joints and connections shall be as specified for underground tanks
points
rust proofing end venting of tanks.
Tanks with bottom more than one foot above the ground
shall have firm foundation and supports of incombustible materials
except wooden cushions. The storage of combustible material within
10 feet of any tank is prohibited. Tanks shall be constructed en-
irely of metal including top, side and. bottom; all openings shall
e gas-tight, exoept breather vent, which shall be screened.. All
anks shall be electrically grounded by resting directly on moist
arth or grounded in accordance with the recm irements for light-
ing protection of the National Fire Protection Association. In
11 locations where above-ground tanks are liable, in case of
reakage or overflow, to endanger surrounding property, each tank
hall be protected by an embankment or 11/10. Such protection shall
'shall
a capacity of not less than one and one-half times the cape-
iity of the tank surrounded, and shall be at least 4 feet high,
'ut in no case higher than one-fourth the height of tank when
.eight of tank exceeds 16 feet. Embankment or dikes shall be made
'.f earthwork or reinforced concrete. Earthwork embankments shall
.e firmly and compactly built of good earth from which stones, ve-
I•etable matter, etc., have been removed, and shall have a flat
section at top of not less than 3 feet and a slope of at least 2
10 1 on both sides. Embankments or dikes shall be continuous, with
o openings for piping or roadways. Piping shall preferably be
I •id over or under embankments; if it is necessary to install pipe
hrough embankments, concrete wing walls shall be provided. Brick
r concrete steps shall be used where it is necessary to pass over
3 - :TANKS INSIDE BUILDINGS. Such tanks shall not be looat-
d above the lowerst story, cellar or basement of building. Tanks
hall be located below the level of any piping to which they may
e connected, or if this is impracticable, satisfactory arrange-
'ients shall be made to prevent siphoning or gravity flow in case
of accident to the equipment of piping. Tanks shall be set on a
firm foundation and those exceeding 2500 gallons capacity shall
be supported independently of the floor construction. Steel
tanks shall be completely enclosed with a heat insulation equi-
valent to reinforced concrete not less than 12 inches in thick-
ness, with at least a 6-inch space on sides between tank and
concrete insulation filled with sand or well tamped earth, and
with 12 inches of sand on top of tank, either between tank and
and concrete slab or above concrete slab.
I
-4
, 4 - LOCATION OF TANKS. If underground tank is within 10
feet of any building and the top of the tank is above the lowest
floor or pit of the building, the tank shall not exceed a capacit
of 50,000 gallons, and must be of metaL,entirely closed in con-
crete without air space. Above ground tanks may be located not
less than 10 feet from line of adjoining property or nearest
building.
5 - PIPING, VALVES, STRAINERS, HEATERS. Cross-connections
permitting gravity flow from one tank to another shall be prohi-
bited except in the ease of outside tanks where this may be per-
mitted through an open connection. All pipe connections to tanks
and other oil containing or using devices shall be made in a sub-
stantial, workmanlike manner. All piping shall be of the standard
full weight wrought iron or steel type for working pressures less
than 100 pounds; for working pressures in excess of 100 pounds,
extra heavy pipe and fittings shall be used. No pipe less than
one-half inch internal diameter will be permitted. Piping shall
be run as directly as possible without sags, and so laid that
where possible pipes pitch toward the supply tank without traps;
provisions shall be made for expansion, contraction, jarring and
vibration. All connections of air lines to burners shall be made
on the upper side and whall extend upward for a distance of at
least 12 inches. Piping for systems with working pressures under
100 pounds after installation shall be tested and proven tight at
a pressure of not less than 150 pounds; where working pressures
exoeed 100 pounds, piping shall be tested andproven tight at a
pressure 50 per cent in excess of the working pressure. No right
and left couplings shall be used, and unions shall be of an
approved type. Piping between any separated oil containing or
using part of the equipment shall be,as fer as practicable, laid
outside of the building underground, and properly protected
against corrosive action; if necessarily inside, it shall pre-
ferably be laid in a trench with proper metal cover; if on floor
or subject or mechanical injury, it shall be protected. Pipes
leading to the surface of the ground or above the floor, parti-
cularly risers to furnaces, shall be protected against injury.
ill and vent pipes shall also be protected. Riser pipes from the
oil supply lines to burner fittings shall be not less than 1 inch
in size. All outside piping shall be laid in solid earth, or in a
trench. Oil pipes shall not be located near nor in the same trench
ith other piping, excepting steam lines for heating. Propping the
pipes on wooden blocks shall be avoided. Openings for pipe through
utside walls below the ground level shall be made oil-tight and
ecurely packed with flexible material. All valves shall be of an
pproved type. Shut-off valves shall be provided on both sides of
ny strainer which may be installed in pipe lines; in discharge
nd suction lines to pump; in discharge and return lines to any
tulle,'
near tank as practicable,and in branch lines near burn-
rs# An outside readily accessible valve shall be provided on all
upply lines entering buildings. In installations where the pump
s located at a distance from the burners, it is advised that a
emote control device be installed so that the supply of oil can
e cut off at the pump in case of accident. A Check valve of an
lipproved type shall be installed in each air line where an en-
losed type of burner is used. A pressure relief valve shall be
installed in supply line to burners and so arranged as to return
urplus oil to supply tank. The use of automatic shut-off valves
or the oil supply is recommended. In systems where either steam
r air is used for atomizing, the oil and atomizing supply shall
e interlocked in an approved manner so that in case of inter-
ption of the atomizing supply, the oil will immediately be out
ff. A test well or gauging device shall be installed, and so de-
igned as to prevent the escape of oil or vapor within the build-
ng at any time. Top of well shall be sealed, and where located
utside of building, kept locked when not in use. Suitable strain-
rs shall be installed in the suction line. Large basket strainers
re recommended in the receiving or filling line of storage tank
111
I
I -5-
1
Ito remove dirt and foreign matter. Where it is necessary to heat
!oil in storage tanks in order to handle it, the oil shall not be
!heated to a temperature higher than 400F. below the flash point,
;closed cup. Heating shall be done by means of properly installed
coils within the tank, using only steam or water. Thermostatic
!!control and thermometer shall be provided for all heating devices.
Heaters shall be of substantial construction; all joints shall be
Omade oil-tight. Only steam, water or approved electrical heaters
( shall be used for preheating. Heater shall be by-passed so that
;in warm weatln r, it will not be under constant pressure while not
'in use.
(o) BUSBERS - PUMPING SYSTEMS. The burner mechanism shall be
Iso designed as to not enlarge the orifice, and so that the needle
!valve cannot be unscrewed and removed in operating. The burner
shall be properly supported, if necessary, independently of the piping. Oil shall be pumped from tank to burners, except where
auxiliary or pressure tanks shall not exceed 60 gallons and auto-
Imatio shut-off is provided at the Burners. Pumps shall be in dup- I
IIlicate, of an approved design, and secure against leaks. Pumps
shall be located in a room cut off from oil burning devices and
provided with entrance which can be reached without passing
through mom where burners are located; if this is not practicable
provision shall be made for.remote control. Pumps used in connec-
tion with the supply and discharge of storage tanks shall be lo-
cated outside embankment walls, and at Bich a point that they will
be accessible at all times, even if the oil in the tank or reser-
voir should be on fire.
(d) DIAGRAM OP PIPING. The contractor installing the fuel oil
equipment shall furnish copies of diagrams showing all of the
main oil lines and controlling valves, and these diagrams shall
be posted where the oil system is installed, and also at some
other point which will be accessible in ease of a fire where the
fuel oil equipment is located.
(a) DOMESTIC OIL BURNING EQUIPMENT. Oil used for fuel under
these rules shall be topped or distilled oil, having a flash point
of not less than 1300F., closed cup. An oil burning system shall
consist of all equipment connected to burner and located within
the building, inoluding auxiliary supply tank and provisions for
filling same, piping, burner, and all accessories. Only systems
approved by the Chief of the Fire Department shall be used.
1 - STORAGE TANKS. Storage tanks shall be located outside
underground, provided, that when the aggregate capacity shall not
exceed 276 gallons, tanks may be located inside of building or
bove ground. The material and construction of outside tanks shall
e in accordance with the requirements for storage tanks for oil
urning equipments. Inside storage and auxiliary supply tanks of
ore than 10 gallon capacity shall be constructed of galvanized
steel, basic open hearth steel or wrought iron of not less than
0.16 U.S. Gauge. Auxiliary supply tanks of 10 gallons or less
apacity may be constructed of brass, copper or galvanized plate
f not leas than No.18 U,S.Gauge. Joints shall be made as specifies
or outside underground tanks in the preceding regulations.
2 - GRAVITY AND PRESSURE TANKS. Auxiliary supply tanks,
ay be of gravity or pressure type, provided that in no case shall
1 he capacity of such tank exceed 60 gallons. If located within a
i uilding, gravity tank shall not be within 5 feet, or pressure
tank within 10 feet, measured horizontally from any fire or flame.
Gravity or pressure tank shall be substantially and rigidly in-
rtalled on incombustible supports in such a manner as to inaire
-6-
protection against mechanical injury. Tanks for wstems under
pressure shall be designed for six times the maximum working
pressure and be tested and proven tight at twice the maximum work-
ing pressure; maximum working pressure shall not exceed 50 pounds.
Tanks shall be provided with a reliable pressure gauge and an
automatic relief valve piped to discharge outside of the building.
Gauging devices or test wells, the breakage of which would permit
the escape of oil or vapor within the building, shall be prohibite..
Auxiliary tanks shall be filled by pumping from storage tanks or
[if gravity or pressure tank contains the entire storage, fill pipei
ishall extend to and terminate outside the building, as provided
!for tanks for oil burning equipments of preceding regulations, and!
in such cases tank shall be so installed that in case of overflow,
oil will not enter building. Auxiliary tanks shall be provided
With an overflow connection draining to storage tank, which pipe
'shall be not less than one size larger than supply pipe from pump.
The overflow pipe of gravity tank shall not be provided with valve:
r other obstructions; but overflow pine of pressure tank and oil
upply pipe shall be provided with inter-connected valves, so de-
igned that the opening or closing of overflow pine shall result
similarly in oil supply pipe.
3 - PUMPS. 0i1 pump used in filling auxiliary tank from
the main storage tank shall be of approved type, secure against
eaks, with check valves located as close to pump as convenient.
umps shall be rigidly fastened in place.
4 - PIPING, VALVES. Standard, full weight, wrought iron
teel or brass pipe with substantial fittings shall be used and
(shall be carefully protected against mechanical injury in a manner
satisfactory to the Chief of the Tire Department. In all piping
systems proper allowance shall be made for expansion and con-
traction, jarring and vibration. All joints shall be made with
.itharge. All piping shall be separated from electric wires not
inclosed in approved conduit, raceways and armored cable, by some
continuous and firmly fixed non-conductor creating a permanent
•eparation, as provided in the National Electrical Code. The use
lif tubing of any kind is prohibited. Supply pipe shall be not less
Than one-fourth inch in diameter, iron pipe size, and when oil is
pumped to the burner, return pipes shall be at least the same size
Wipe connections to tanks shall be suitably reinforced, and proper
llowance made for expansion and contraction, jarring and vibratio..
µpenings for pipes through masonry walls below the ground level
shall be made oil-tight and securely packed with flexible mater-
ial. All connections shall be made perfectly tight with well fitt
points. Unions shall be used at burners to facilitate removal. All
unions shall be of approved type, having conically faced joint,
obviating the use of packing or gaskets. Pining shall be run as
directly as possible, and in the case of pumping systems, so laid
that if practicable the pipes are pitched back toward the storage
tank without traps. Systems under pressure shall be designed for
six times the working pressure and installation when complete
shall be tested and proven tight at twice the maximum working
pressure. Readily accessible valves shall be provided near each
burner and also close to the auxiliary tank in the pipe line to
burners. Control valves shall be of approved type provided with
stuffing box of liberal size, containing a removable cupped gland
designed to compress the packing against the valve stem and
arranged so as to facilitate removal. Valve shall be designed to
close against the supply, and to prevent withdrawal of stem by
oontinued operation of the handwheel. The use of packing affedted
y the oil or heat is prohibited. The size of the orifice through
hieh the oil is supplied to the burner shall be limited to furniso
my sufficient oil for maximum burning conditions when the con-
trolling valves are wide open. Valves shall be arranged so as not
to enlarge the orifice.
I
-7-
5 - BURNERS, INSTALLATION. Suitable automatic shut-off
to prevent abnormal discharge of oil, at the burner shall be pro-
vided for all systems. Burners containing chambers which allow
the dangerous accumulation of gases, or conveying pipes or parts
!which, when subject to intense heat become stopped up due to car-
bonization, are prohibited.. Burners shall be so designed as to
permit of ready cleaning and not allow the leakage of oil. Auto-
matic systems shall be so designed that the flame cannot be ex-
tinguished by operation of the automatic control valve, unless a
pilot light shall be provided in the combustion chamber. Previous
Ito the installation of the burner, the ash door of the furnace
shall be permanently removed, or bottom ventilation otherwise
provided to prevent the accumulation of vapors within the ash pit.
Stoves or ranges originally designed for use of fuel other than
oil should not be used in connection with oil burners unless
spaces in which vapors might collect are adequately vented. No
(damper shall be permitted in the chimney uptake that may entire-
ly shut off the passage of fumes or gases up the flue. No com-
bustible material shall be stored within 10 feet of furnace door.
(Near the furnace, and so located as to be convenient for use in
emergency, there shall be provided a hand fire extgnguisher of
approved type suitable for use on oil fires. A card giving com-
plete instructions in regard to the care and operation of the
system shall be permanently posted near the apparatus. Said card
shall be placed under glass and framed. Oil burning equipment
shall be installed only by properly qualified meohan&cs experienc-I
ed in this kind of work.
(f) PERMITS FOR CONSTRUCTION. No new plant, or any recon-
struction of any old plant, using oil for fue;.,for producing
power or heat, or either of them, shall be constructed, enlarged,
altered, operated or maintained in the city until plans and speci-
fications of the same have been filed by the owner, agent or corn
tractor in the o:ffloe of, and approved by the Chief of the Fire
Department, and a permit issued by him for suoh construction, re- !
construction or maintenance. The plans and specifications to be
filed with the Chief of the Fire Department shall show a diagram o
the piping, looation, setting and capacity of tanks, burners and
pumps, and all other information required by the Chief of the Fire
Department.
(1) Upon the approval of such plans and specifica-
tions, a duplicate set of which shall be left on file in said off-
lice, and upon the payment of the fees hereinafter provided, the
(Chief of the Fire Department shall issue a permit for the construc-
tion, erection or maintenance of such plant. As soon as the Chief
of the Fire Department has issued a permit as above provided, it
shall be his duty to see that the execution of the work permitted
lis carried out in conformity with the plans and specifications.
(2) It shall be unlawful for any person to use any
ew or reconstructed plant, using oil for fuel until he shall first
ave procured the final certificate from the Chief of the Fire De-
artment that the plant is constructed in accordance with the plan
nd speoifications filed with the Chief of the Fire Department at
he time the permit was issued.
(3) FEES DOR INSPECTION. A fee shall be charged
or the inspection of plans and specifications for the construe-
ion, reconstruction or alteration of any plant, which fee shall
noluded the issuing of permit and certificate in case such are
ranted, as follows:
For plants in residences $2.00
• For all plants except in residences 05.00
Said fees shall be collected by the Chief of the
ire Department and by him paid into the City Treasury. Section
1 147 does not apply to cases where this fee is paid.
•
i
-8
SECTION 2. In the opinion of the Board of Commissioners,i
1 it is necessary to the peace, health and safety of the inhabitantle
1 of Salt Lake City that this ordinance become effective immediate) ,
1
! SECTION 3. This ordinance shall take effect at once
upon its publication.
l
III
1
I
Passe by the Board of Commissioners of Salt Lake City,
Utah, this \\ day of G \Ja , A. D. 1925.
l
( 7iliG � L -1
Mayor.
City Recorder
1
1
I
I
la& fldlu _ j!),41RIP r
37
Ordinance
r -t
ttoNtt. oft t
r I • IN 0
r.P
...
T .
•
• first tPUI)1iCatiOin
iL ll
lJ
&u /2.1025
CITY RSCORDER