Loading...
38 of 1932 - Adopting a Standard Code for Installation of Gravity Warm Air Heating Systems. ROLL CALL VOTING r AYE NAY Salt Lake C;ty Utah NOV 171932 - 193 Finch I move that the etr he adopted Keyser _f Knight t/ Y Lake Mr Chairman . F—IgnILIT LW— Result AN ORDINANCE ADOPTING the Standard Code for the installa- tion of gravity warm air heating systems in buildings used for human habitation and providing penalties for the violation of the previsions of said Code. Be it ordained by the Board of Commissioners of Salt Lake City, Utah Section I. That the eighth edition of the Standard Code Regulating the Installation of Gravity Warm fir Heating Systems in buildings used for human habitation adopted, approved and issued by the National Warm Air Heating Association, Inc , the American Society of Heating & Ventilating Engineers and the National Asso- ciation of Sheet Metal Contractors is hereby adopted by Salt Lake City as the ordinances, rules and regulations pertaining to and regulating the installation of warm air heating systems in all buildings used . . for human habitation in said city, provided that Article 3 of said Code is hereby amended by adding to said Article a new Section to 10 be known as Section 3A, which shall read as follows 3A In determining the B t. u loss of any structure com- ing under this code by the use of the constants and rules set out in this article (Article 3) it is definitely recognized that these apply to the ordinary building when the aforesaid rules and constants are applied to the individual room and the total heat loss for the structure being the summation of the heat loss developed by each individual room Where a structure differs from the ordinary residence, that is where the exposure is great- er than that of the ordinary residence or where more. than two air changes per hour are required the foregoing rules shall not be used, but the total heat loss in B.t u is per hour shall be de- termined by the standard method using coefficients of heat trans- 38 -3- I ney shall be such so that when a furnace is installed the height of said chimney will be not less than 3lfeet above the grate of said furnace SECTION 2. All gravity Warm Air Heating Systems installed , in buildings used for human habitation in bait Lake City and all installation and construction work incidental thereto shall strictly (comply with and conform to the provisions of the Standard Warm Air Heating Code and amendments adopted in Section I of this ordinance SECTION 3 This Code may be cited and designated as the Standard Warm Air Heating Code. SECTION 4 Any person violating any' provisions of this ordinance or any of the provisions of the Standard Warm Air Heating Code shall, upon conviction thereof, be punished by a fine in any sum not exceeding One Hundred Dollars (0100 00), or by imprisonments! in the City Jail for a period not exc,ed3,ng thirty (30) days, or by' both such fine and imprisonment The court may, in imposing a fine, enter as part of the 3udgment that, in default of payment of the fine, the defendant may be imprisoned in the City Jail for a period ,not exceeding six months. SECTION 5 In the opinion of the Board of Commissioners, it is necessary to the peace, health and safety of the inhabitants of Salt Lake City that this ordinance take effect immediately. SECTION 6 This ordinance shall take effect upon its first publication. )� j Passed y the Board of Co issioner of Salt Lake City, Jtah, on the f 7' day of 1932 ; A ze11 Q� _. emporary Chas at ity Recorder. 1 t -2- fer Should it be desired to construct a building whose wall construction does not come under one of the classifications set out in this Code the City Engineer shall determine or shall be assured to his entire satisfaction as to the coefficient o heat transfer for such material or such combination of mater- ials and such coefficient of heat loss shall be used in deter- mining the total B.t u 's to be provided for by the furnace I And Article 3 is further amended by adding to said Article a new Section to be known as Section 10, which shall read as follows, to-wit: SEC 10 All warm air heating furnaces installed within i the corporate limits of the City of Salt Lake and coming with+ in this Code shall be rated in terms of B t u output by the City Engineer or his authorized representative when said fur- naces are used to burn fuels ordinarily available in the City, of Salt Lake, the term "fuel" being defined for purposes of this code as bituminous coal, coke, fuel oil or gas In the event that the City Engineer has not been satisfied as to the rating of any warm air heating furnace offered for installa- tion within the corporate limits of the City of Salt Lake or combination of such furnace and stoker, in B.t u.'s at the bonnet, then in that event he shall rate said furnace accord ing to formula and rule set out in Section 9 of the Standard Code Regulating the Installation of Gravity Warm Air Heating Systems for Residences And said Code is further amended by eliminating entirely therefromil Article 5 and in lieu thereof Article 5 shall read as follows Article 5 Any structure coming within this Code shall be provided with a chimney which shall be constructed in con- formance with "A Standard Ordinance for Chimney Construction"I recommended by the National Board of Fire Underwriters third edition revised 1927 The minimum net dimension of such chim- ney shall not be less than 12 inches nor shall the cross sec- tional area be less in square inches than the total B.t u loss of the structure divided by 1900 The minimum height of chiml pf YI r_,_ , : ..., - ' , fS _,_ t, I _, - _ s.f ,: .~sl f R ) (y= Z `� 1::' � a v < K II : I ]]' I_ V _- JAM r The Standard Code REGULATING THE INSTALLATION OF GRAVITY WARM AIR HEATING SYSTEMS IN RESIDENCES - - EIGHTH EDITION - HEAT 9� CLEAN AIR THIS SYMBOL IS THE IDENTIFYING MARK OF THE DEALER WHO IS PLEDG- ED TO INSTALL WARM AIR SYSTEMS ACCORDING TO THEEATING SPECI- FICATIONS OF THIS STANDARD CODE. Printed in U.S.A. EIGHTH EDITION Aug.1,1931 Standard Code Regulating the Installation of Gravity Warm Air Heating Systems In Residences This Code Is approved and tutted by authority of the: National Warm Air Heating Association, Inc. Office of Managing Director 3440 A.I.U.Bldg. Columbus, Ohio The American Society of Heating and Ventilating Engineers Office of Secretary. 51 Madison Ave. New York, N. Y. National Association Sheet Metal Contractors Office of Secretary, 429 Fourth Ave. Pittsburgh, Pa. Additional copies Al a Cade S may be secured from any of Quantity ord..s can be secured from McMullen Printing Co. 4000 Laclede Ave. St.Louis,Mo. /xi What The Standard Code Is The Standard Code is,as the full name implies, a set of rules to govern the proper installation of Warm Air Heating Systems in Residences. A Warm Air Heating System consists essential- ly of a furnace,with casing and smoke pipe, to- gether with a properly designed system of heat- ing pipes and outlets,known as registers;also air ducts to convey the unheated air to the furnace. The average home owner does not realize that the proper design and correct installation of heat- ing pipes is an essential part of the heating system. No matter how well the furnace is made it cannot give its full service unless it is properly installed. For over twenty-five years,the Manufacturers of warm air furnaces, Engineers, and Installers have made numerous efforts to establish a practical set of rules that would govern the instal- lation of Warm Air Heating Systems. This was done to protect the public against wrong instal- lations. As nearly three out of every four homes in which a central heating system is installed, use this most flexible system,some protection to the home owner is needed. The enclosed rules have been established after many meetings and a complete study of the situation in all parts of the United States, together with years of research work at the ' University of Illinois. The authority back of this code is shown on the preceding page. The National Warm Air Heating Association, Inc.represents approximately 90% of the out- put of warm air furnaces. (3) 1, The American Society of Heating and Ventilat- ing Engineers represents over 2000 Heating and Ventilating Engineers. The National Association of Sheet Metal Contractors represents over 7000 Sheet Metal Contractors and Furnace Installers. This Code now makes it possible for the home owner to check over his own heating plant and to observe whether the installation of the heating plant has been made correctly and in a safe manner. Every person who intends to install a warm air heating system in either a new or old house owes it to himself to specify that it shall be "Installed According to the Standard Code." Only those installers who have pledged them- selves to install warm air heating systems ac- cording to this Standard Code are entitled to use the symbol shown on the front cover of this booklet. It is your protection and you can be sure of receiving a"code"installation by dealing with a dealer or manufacturer who displays this symbol. Such an installation is triply endorsed by the Installer,the Furnace Manufacturer and the National Warm Air Heating Association. EIGHTH EDITION Standard Code Regulating the Installation of Gravity Warm Air Heating Systems in Residences The Eighth Edition of the Standard Code supersedes all previous issues and contains corrections to date. 1st Edition issued Oct. I, 1922 2nd Edition issued Feb. I, 1923 3rd Edition issued June I, 1924 4th Edition issued May I, 1927 5th Edition issued Mar. I, 1928 6th Edition issued Mar. I, 1929 7th Edition issued Sept. I,1930 8th Edition issued Aug. I, 1931 (4) ARTICLE No. 1 Meaning of the Term "Gravity Warm Air Furnace Heating System" Gravity Warm Air Heating Systems, to which this code refers, shall consist of one or more warm air furnaces, enclosed within casings, to- gether with necessary appurtenances thereto, consisting of warm air pipes and fittings, cold air or recirculating pipes, ducts, boxes and fit- tings,smoke pipes and fittings,registers,borders, faces and grilles, the same being intended for heating buildings in which they may be installed. ARTICLE No. 2 Certified Measurements Certified measurements on warm air furnaces together with the name and number of that furnace,will be issued by authority of the Nat- ional Warm Air Heating Association, when, if and as,the grate areas and heating surfaces have been accurately measured and approved by the Research Advisory Committee. (s) 3 ARTICLE No.3 Method for Determining Sizes of Warm Air Pipes, Wall Stacks and Furnaces for Use in Residences Method for Determining Sizes of Basement Warm Air Pipes Section 1. Each First Floor Room. Divide square feet of exposed glass by 12, Divide square feet of net exposed wall,ceiling or floor by factors in Table A. Divide cubic contents by 800,(Note 6) Add together the above and multiply by 9. The result is the area of the basement pipe in square inches. Stated as an equation,this is, The sum of: Glass(eq.ft.)(NoteI)+11 l Net Watl(sq.ft.)(Noteto 2)+( .' (,A).x9=Area of Cu.Content.(Note6)+800 Baem't. Pipe Section 2. Each Second Floor Room Divide square feet of exposed glass by 12, Divide square feet of net exposed wall,ceiling or floor by factors in Table A. Divide cubic contents by 800, (Note 6) Add together the above and multiply by 6. The result is the area of the basement pipe in square inches. (See Art.3 Sec.9, (c). Staled as an equation,this is, The sum of: Glass (eq.ft.)(Note I)+12 es o Net Wall(eq.ft.)(Note 2)+ Table n) x6.Area of Cu.Contenm(Note6)+800 Baem't.Pipe Section 3. Each Third Floor Room Divide square feet of exposed glass by 12, Divide square teet of net exposed wall,ceiling or floor by factors in Table A. Divide cubic contents by 800, (Note 6) Add together the above and multiply by 5. The result is the area of the basement pipe in square inches. Staled as an equation,MI,is, 1 , The Sum of: Glass(eq.ft.)(Note 1)+12 l Net Wall(eq.ft.)(Note 2)+(T.bie"Z)J x5.Area of Cu.Content.(Note 6)+800 Basm't.Pipe JJJ (6: Basis of Working Rules for Pipes (Section 1-2-3) (a)These formulae are for 70 degrees temperature difference(outside temperature zero,inside temp- erature 70 degrees Fahrenheit). When temperature difference is more than 70 degrees,add I M%per degree above 70°to final figures. When temper- ature difference is less than 70 degrees, deduct I%%per degree below 70°from final figures. (b) The values as given in Table A for use in the working rules. Article 3,Sections I -2 and 3 are derived as follows: EXAMPLE: The unit of calculation adopted for this is the equiva- lent of 1000 b.t.u. transmitted. Any other number than 1000 might be selected if desired and the result would be the same. Calculations are based on the commonly accepted data for heat loss through different types of walls. Thus,the factor 60,Item No.I,Table A,is obtained in the following manner:The rate of heat transmission through a wall consisting of siding,paper. sheathing,studding,lath and plaster, is 0.238 b.t.u. per square foot,per hour,per degree difference between room and outside temperatures. At 70 degrees inside and zero outside,one square foot of wall will transmit 0.238 x 70=16.66 b.t.u. per hour. 1000 b.t.u.will then be lost through 1000+I6.66=60 square feet of wall. Since it is found from experiment that one square inch of first floor leader pipe delivers III b.t.u.,it will require 1000*I11=9 square inches to compen- sate for the loss through 60 square feet of wall. From this we derive the formula: 60 a 9 =Area of first floor leader Substituting 167 for the second floor and 200 for the third floor in place of III, gives the factors 6 and 5 respectively. Other values in Table A for the different types of walls were obtained by substitution of proper coefficient of heat transmission instead of 0.238 in the above formula. Co-efficients used in Table A taken from A.S.H.& V.E. Guide 1929. TABLE A (The factor 60 used in the above example,is for buildings constructed as in item No.I (a). When other types of walls are used substitute the appro- priate factor as given below). Exposed Wall FACTORS No. I-(a) Frame Wall constructed of siding,paper, sheathing,studding,lath and plaster 60 (b) Same(I-a)construction substituting fibrous board or equivalent for the lath. 80 • (c) Same(I-a)construction with additional.. 33)"insulating fill between studding 140 For stucco on frame walls, use the same values as for frame with siding,as shown in 1-(a),I-(b)and I-(c). No. 2- 9"Brick wall plastered on one side 40 No. 3-(a) 9"Brick wall,air space,furred and plus-. tered 57 (b) Same(3-a)construction substituting%" fibrous board or equivalent for the lath 84 No. 4- 13"Brick wall,plastered on one side 52 No. 5-(a) 13"Brick wall,air space,furred and plastered 69 (7) ) 3 (b) S e(5-a)construction substituting 3" fibrous board or equivalent for the lath 97 No. 6- 4"brick,4"or 8"hollow tile plastered 57 No.7—(a) 4" brick, paper, sheathing, studding, lath and plaster.(brick veneer) 58 (b) Same(7- )construction substituting%" fibrous board or equivalent for the lath 84 (c) Same(7-a)construction with additional 3 y"insulating fill between studding 158 No.8— Stucco on 8"Hollow tile.and plaster 48 No.9—(a) Stucco on 8" Hollow tile, furred and plastered 65 (b) Same(9-a)construction substituting%" fibrous board or equivalent for the lath 95 CEILINGS WITH ATTIC SPACE ABOVE No.I0-(a) Lath and plaster without floor above 50 (b) Same (10-a) construction substituting %" fibrous board or equivalent for the lath 70 (c) Same(10-a)construction with additional 3."fibrous board or equivalent nailed on top of joists 90 (d)Same(10-a)construction with additional 3Y"insulating fill between joists 150 No.I I-(a) Lath and plaster with tight floor above 90 (b) Same (I I-a) construction substituting t,"fibrous board or equivalent for the lath 104 (c) Same(I 1- )construction with additional 3 M"insulating fill between joists 183 No.I2-(a) Metal without floor above 40 (b) Same(I2-a)construction with additional 34"fibrous board or equivalent between metal and joists 65 (c) Same(I2-a)construction with additional %" fibrous board fastened on top of joists 85 (d) Same(I 2-a)construction with additional 3)z"insulating fill between joists 145 No.13-(a) Metal with tight floor above 75 (b) Same(13-a)construction with additional H."fibrous board between metal and joists 95 (c) Same(13-a)construction with additional 334"insulating fill 176 CEILINGS WITHOUT ATTIC SPACE ABOVE—PART OF THE ROOF No.I4-(a) Lath,plaster,rafter,sheathing,any type of shingles or roofing 57 (b) Same (I4-a) construction substituting 34"fibrous board or equivalent for the lath 74 (c) Same(14-a)construction with additional 3%"insulating fill 130 FLOORS OVER EXPOSED OR UNHEATED SPACES No.15-(a) Double floor,on joist, 42 (b) Same(15-a)construction with additional %"fibrous board fastened to bottom of joists 88 (c) Same(15-a)construction with sheathing fastened to bottom of joists and with additional 33/"insulating fill between joists 140 The substitution of 34"insulating materials for sheathing should not be considered as having any additional insulating value. !s) 21 Explanatory Notes Note I. In obtaining glass surface use full Be- ment opening. An outside door is figured as glass. Note 2. To obtain net outside wall multiply height by width and deduct all windows and outside doors, as obtained in Note I. For all rooms with attic spaces immediately above,full ceiling areas shall be taken into account, using table A. Floors over unheated spaces shall be taken into account, using Table A. For walls and doors between heated and unheated spaces—use 50%of similar outside ex- posure. Note 3. For rooms having unusual exposure, (ordinarily north,northeast and northwest,)add 15% to the calculated pipe area. Note 4. Use no basement warm air pipe less than 8 inches in diameter. If a basement warm air pipe figures not to exceed 10% greater area than any standard commercial size th n the nearest commercial size shall be used, provided however, that the total leader pipe area for each floor shall in no ase be less than the total calculated requirements according to Sec.I.2 and3. Note 5. It is understood in using the above values for determining basement warm air pipe areas,that these pipes should be run comparatively straight and that they should not be over 12 feet in length.Sharp turns and long pipes should have extra capacity. When warm air pipes exceed 12 ft. in length or have more than two 90 degree turns,the next larger commercial size pipe must be used. Note 6. The value of 800(used in cubic contents) is for an estimated air change of one room volume per hour. To provide for 1 t/a room volume use the figure 600. For 2 room volumes use the figure 400. Size of Wall Stacks Section 4. First Floor Rooms. Same as Section I.All first floor fittings and • connections,shall maintain a free area equal to the round basement pipes leading to them. Section 5. Second Floor Rooms. Not less than 70%of calculated basement pipe area as determined in Section 2. Section 6. Third Floor Rooms. Not less than 70%of calculated basement pipe area as determined in Section 3. Section 7.(a)Where two or more rooms are heated from the same basement pipe and stack, the area of such basement pipe and stack shall equal the combined areas as de- termined in Article 3,Sections I,2,and 3. (b) Transition from warm air pipes to stacks or register heads shall be made with a well designed elbow or boot. Size of Registers Section 8. All registers shall have a free area at least equal to the area of the basement pipes leading to them, and shall be of the approximate width of the stacks or fittings to which they are attached. (9) Size of Furnace. Section 9. (a) Add together the leader pipe areas(expressed in square inches)necessary for heating the building, as determined by the foregoing calculated requirements,Art. 3,Sec. I,2 and 3. and install a furnace. rated by the following formula: Furnace Rating Formula L= 1.75 G [I + 0.02 (R—20)] L =square inches of warm air pipe connected to the furnace as calculated. G=grate area in square inches;the area of the fire pot at the grate level,its most restricted area. R=ratio of heating surface area to grate area; 1.75 =a constant based upon the results ob- tained in the Association Research on a furnace having 20 square feet of heating surface for each square foot of grate. The above equation is based on the:— efficiency of heater 0.55;combustion rate of 7.5 pounds of coal per sq. ft. of grate per hour; calorific value of fuel 12,790 B.t.u. per lb.;percentage of heat available at regist- er 0.75; average B.t.u.delivering value of one sq. inch of leader pipe area, assuming half of the heat is sent to each floor, 136; and on an operating temperature of 175 deg.F.at the register. The formula allows 1.75 square inches of warm air pipe area for each square inch of grate area, for the furnace having a ratio of heating surface to grate surface of 20 to I. For furnaces having other ratios of heating surfaces to grate surface, it adds 2 per cent or deducts 2 per cent for each unit above or below a ratio of 20. Application:- No.I No.2 No.3 Positive No Negative Correction Correction Correction Grate area.eq.in. = 346 346 346 Heating surface area Lt in. = 7540 6920 5665 Ratio heating surf ace area to grate area = 21.8 to I 20.0 to 1 16.4 to I R—20 = 1.8 0.0 —3.6 Correction per cent= 3.6 0.0 —7.2 1.75 G = 606 606 606 L= 1.75 G+cor- rection = 628 606 562 (b) Every warm air furnace shall be equipped with a water pan or other humidifying device. not Second Floor Heating (c)In second floor duplex, flats or apartments where separate heating plants are used, add 50%to the total net calculated areas as determined in Art.3,Sec. 2. This represents the required furnace capacity in square inches of leader pipe area. Leaders and stacks are not to be increased. Gas or Oil-Fired Furnace (d) In the application of any gas or oil-fired furnace to any warm air heating system, any deviation from the Standard Code shall apply only to the furnace itself. Limitations of the Code (e) The formulas for determining the size of basement warm air pipes are applicable to rooms of the proportions found in the average residence. For rooms having ratios of glass to cubic con- tents falling outside of these average proport- ions, adjustment must be made in the number of air changes to be used.The formulas are not applicable to pipes having diameters greater than 14 inches or lengths greater than 12 to 16 feet. The rating formula is applicable to furnaces of the common type of construction having round firepots and ratios of heating surfaces to grate area between 15 and 30. The formula is not applicable to furnaces of special conttruct- ion, or equipped with unusual special features, to ratios outside of 15 to 30, nor to coals de- viating materially from 12000 B.t.u.per pound. ARTICLE NO.4. Installation Location of Furnace Section 1. The location of the furnace shall equalize the length of warm air pipes as far as possible, yet give necessary preference to pipes supplying rooms having unusual requirements. Foundation Section 2 (a) Furnace foundation of brick, cement,or other like incombustible material must be provided. Said foundation shall extend at least fifteen inches (15") at rear and sides of furnace casing and at least thirty-six inches (36") in front of furnace casing. Foundation to be level. (See Art.5). (b) Where it is necessary to place a furnace on a combustible floor, not less than four inches (4") of hollow tile shall be used in every instance, having joints matched in such a way that air passage will be free from side to side,so that at no time will the p4 • irs �r1 ' E+ ! 3 removal of ashes or the handling of coal close up these openings. Such foundation shall be constructed upon,and covered with continuous sheet metal plates, of not less than No. 24 gauge metal,having all joints substantially riveted or double seamed and the bottom sheet to have the edges turned up at least one inch. This floor covering shall extend under the whole of the fire box and ash pit of the furnace and outwardly not less than 12 inches on all sides and rear of casing or base ring and 36 inches in front. Setting or Assembling of Furnace Section 3. (a) The base ring of any portable warm air furnace shall be cemented to the foundation, and cement flushed in around the back of the base ring, making an air- tight joint. The furnace parts shall be assembled plumb and level and in a work- manlike manner. (b) All sections and joints shall be proper- ly fitted. Joints requiring cement shall be well filled and all bolts shall be drawn up tightly. Casings Section 4. (a) Warm Air furnaces shall be en- closed in metal casings or walls of brick, tile or concrete. (b) Portable. Sheet metal casings including casing tops or bonnets shall be made of gal- vanized sheets, not lighter than 26-U. S. Standard Gauge. They shall fit the castings and casing rings closely, so as to be dust tight,and shall be securely fastened to the front. The casing shall be lined from the upper casing ring down to a line on a level with the grate. (c) When side collars are used the casing top or bonnet must be of sufficient height so that the largest warm air pipe can be taken from side without ovaling. In no case shall a distance less than eight inches(8")be main- tained between the top of any furnace and the bonnet. (d) Any furnace, the casing top of which shall come within twelve inches (12") of a combustible floor, ceiling or joist, shall be protected by a metal shield, extending not less than eighteen inches (18") beyond the casing of said furnace. This shield shall be suspended at least two inches below wood work,allowing free air space between shield and woodwork. No furnace casing or top, (12) coming nearer than six inches(6")of ceiling or joists shall be allowed in any case. All metal casing tops shall be insulated with an air space or covered with magnesia,asbestos boiler covering or sand. (e) Openings for side casing collars shall be cut into the casing top or bonnet,so that the tops of all openings are on a level. Casing collars shall be fitted into place with a proper flange, or bead on the outside and drawn up on the inside, making a dust- tight joint. All collars shall be of same size as the warm air pipes to which they are to be connected. (f) Brick, cement or hollow tile casings shall be constructed as follows: Walls shall be not less than eight inches(8") in thick- ness, and shall be constructed air tight. The least inside dimension of rectangular casings shall be the same as that of the portable casing of a corresponding size of furnace. Walls shall be carried to the same height as the portable walls, allowing not less than eight inches(8")between the top of the furnace and the bottom of the top cover. After placing the collars for the warm air pipes, continue the masonry up 2" above the top of the collars, lay angle or tee irons across the furnace top, spaced 8",cover these with sheet metal not less than 26 U. S. S. gauge,cover the sheet metal with masonry or sand and run the side walls four inches (4") above the roof of the furnace.A galvanized iron casing bonnet may be used on a brick set furnace. Provision shall be made in the walls for a manhole to give ingress to heater. Warm Air Pipes in Basement Section 5. (a) All warm air pipes shall be made of bright tin not lighter than IC,or galvan- ized iron. Side seams shall be locked seams. All joints shall be either double seamed or lapped not less than one and one-quarter inches(I)"). Such joints shall be match- beaded,or beaded and soldered,or riveted. All pipes and fittings shall be properly secured to ceiling or joist. No solder or riveted joint is required where round pipe slips over the casing collar or enters boot or box. Any pipe twelve inches (12") or greater in diameter shall not be made of material lighter than IX tin or No. 26 U.S.Standard Gauge galvanized iron. (b) All warm air pipes in the basement (13) tl `.d shall have an upward pitch of not less than one inch(I")per running foot. (c) No warm air pipe shall run within one inch (I") of any woodwork unless such woodwork is covered with asbestos paper and the paper covered with tin or iron. (d) All warm air pipes in the basement shall be provided with dampers supported on both sides not more than two feet from the casing. (e) Where warm air pipes pass through a masonry wall, a metal thimble shall be provided, having a diameter at least I" greater than the pipe, and pipe supported in such a manner that the air space is uniform on all sides. (f) Where warm air pipes pass through or into unheated spaces separated from the furnace room they shall be insulated with not less than three layers of air cell as- bestos paper or the equivalent. Wall Stacks Section 6. (a) Single Stacks. All single wall stacks or wall pipes,heads,boots,ells,tees, angles and other connections shall be made of tin or galvanized iron and shall be covered with not less than one thickness of 12 lbs.per one hundred(100)square feet of asbestos paper. All such stacks shall be braced in a proper manner so as not to obstruct the flow of air but to retain the full capacity throughout. All joints shall be locked and held in place by means of lugs,or straps. No joint,either horizontal or vertical,shall depend wholly upon solder to make it tight. An air space of not less than five-sixteenths(5/16)of an inch shall be allowed on the two sides nearest the verti- cal studs. See also(d). (b) Double Stacks. All double wall stacks or wall pipes,heads,boots,ells,tees,angles and other connections shall be made of tin, not lighter than IC or galvanized iron and shall be made double, from and including the boot or foot piece in basement to the top of each and every stack and register head on all floors. There shall be uniform air space of not less than five- sixteenths (i"s) of an inch, which must be maintained between the outer and inner walls of all such pipes and fittings of all kinds, styles and descriptions;such pipes, heads, boots and other fittings to be of the styles, or equal to those accepted by the National Board of Fire Underwriters. un (c)All stacks and fittings either single or dou- ble must be secured firmly in place by lugs or straps attached to the outer walls of stacks and fittings, and no nails shall be driven through these stacks or fittings at any point. No lugs or straps shall be formed by cut- ting holes in outer walls of stacks or fittings. No wall pipes or fittings shall be used which depend wholly on soldered joints. The various members shall be so made that all joints are locked or soldered and the several members shall be attached to each other with slip joints, which are, for the purpose intended,air tight. (d) Where stacks, heads, boots or other fittings, whether double or single, go through the first floor, all openings around such heads, boots, stacks or fittings must be filled with asbestos cement or other in- combustible insulating material to make the openings gas and dust tight. In no case shall any metal surface of stacks,heads,boots or other fittings conveying heated air come in contact with any wood girder,joists or floor- ing of the first floor. Registers Section 7. (a) When baseboard or wall registers are used, they shall be properly sealed to the stack head in such a manner as to prevent any leakage of air between the head and the register. (b) Floor registers shall be provided with double register boxes of tin or galvanized iron with an air space of not less than five- sixteenths (ss) of an inch between inner and outer boxes;or,where single boxes are used,they shall be insulated from the wood or other combustible material by asbestos paper covered with sheet metal,or by the use of register borders. (c) Registers for warm air, and warm air pipes,stacks and fittings shall not be located in outside walls, unless properly insulated with 1" air cell covering or its equivalent. (d) Any furnace system having not more than two warm air openings,at least one of these openings shall be without valve or louvers and the pipe thereto shall be with- out damper. Air Supply to Furnace Section 8. (a) The air supply to the furnace may be taken from outside or from within the building or may be taken partially from outside and partially from within. In no (is) ) case, however,shall air be supplied to any furnace from any basement or furnace room, not occupied as living quarters. (b) The cold air intake or return where air is taken from within the building shall have a net area throughout its entire length of not less than the combined net area of all warm air pipes leading from the furnace. This may be maintained in one or more ducts. No reverse incline or air trap will be allowed in any section thereof. (c) When the cold air supply is taken wholly from the outside of the building the supply duct at its most contracted area must equal or exceed eighty per cent(80%) of the combined area of all warm air pipes leading from the furnace. (d) Cold air ducts,except as stated in(f), shall be constructed of metal, tile or other non-combustible material having smooth inner surface and shall maintain a constant net area throughout their entire length.All joints shall be made dust tight. Horizontal rectangular return ducts shall have at least 10% greater area than vertical connecting pipes. (e) Where a boot or shoe is connected to the casing at the base, the opening shall not extend higher than a line on the level of the top of the grate of the furnace.The width of the shoe shall be of proper measurement to make the area at all points at least equal to that of the round or square pipe to which it is connected. This boot or shoe shall be of streamline transition construction. (f) Wherever the space between joists is used to convey cold air over head, all bridging and bracing shall be removed and a sheet metal pan shall be constructed to extend not less than two inches (2") below said joists. The connection from this pan to the boot or shoe shall be made of galvanized iron not lighter than No. 26 U. S. Standard Gauge, and shall have a transition fitting, the top area of which shall be at least 10%greater than the area of the connecting pipe. Note 7. To reduce friction, and for the sake of cleanliness,it is recommended that the Joists and all wooden surfaces between such Joists be lined with metal. (g) When it is necessary to set the furnace over a pit and connect up cold air under the basement floor,such pit or cold air trench shall not exceed eighteen inches (18") in (16) depth below the casing base ring and the width of the trench or trenches shall be of proper measurement to make the area at least 10%greater than the pipe to which it is con- nected. The connection between the cold air pipe or duct and the underground pit shall be made with a transition fitting as described in"(f)"of this section. (h) The cold air face or faces shall be made of wood,or metal. When set in floors the top of same shall be flush with floor. Where cold air face is placed in a seat or side wall (whether furnished by owner, general con- tractor or furnace contractor) the open work of face must extend to within at least one inch(I")of the floor line. The free area of cold air faces shall be at least equal to the free area of the duct or ducts to which they are connected. (i) The effective area of a vertical cold air face lies within fourteen inches(14")of the floor line,hence,the capacity of any vertical cold air face shall be determined by multi- plying the base line in inches by not to ex- ceed fourteen inches(14")in height and de- ducting for the grills or cross bars. (j) When a fan is installed in the air supply duct of a gravity system the same net area of all ducts shall be maintained as calculated under Article 3,Sections I, 2 and 3 and Article 4,Section 8(b). Smoke Pipes Section 9. (a) The smoke pipe shall be as short and direct as consistent with the location of the furnace. It shall be made of metal not lighter than No. 24 U. S. Standard gauge, and not less than the full size of the collar on the furnace throughout its entire length. It must have no opening for attaching any fire place, stove, range, water heater,gas or ventilating connection. It shall be lock seamed or riveted: all joints shall lap not less than one and one-half inches (1%") and it shall be rigidly secured. Cast iron smoke pipe may be used. (b) All smoke pipes shall be provided with check dampers, placed on the side of the pipe or at the end of a tee; when cast iron smoke pipe dampers are used they must be placed between the check damper and the furnace and supported on both sides of the pipe. (c) Where the smoke pipe enters the flue,a (1r) 1f, 1" i'.i thimble shall be cemented into the flue(See Art.5 (c) k and the connections thereto made air tight. Should any smoke pipe come within eighteen inches (18") of any combustible material, such combustible material must be covered with asbestos paper and a metal shield so fastened that a two inch air space exists between this shield and the combustible material. This shield shall be no less in size than twice the diameter of the smoke pipe and of sufficient length to cover the combustible material at all points. (d) No smoke pipe shall project through any external wall or window. No furnace connection is to be made to a flue without a cast iron or steel cleanout having first been provided in the flue, (not more than eight inches(8")below the smoke pipe opening). The base of the flue shall be filled up to the bottom of the clean out:all of which must be made air tight. Room Heaters Section 10. Whenever furnaces or room heaters are supported by legs not less than five inches (5") high, and set on a combustible floor,the floor under same shall be covered with non-combustible material, extending not less than twelve inches (12"), on sides and back of heater and thirty-six inches (36")in front of said heater. Pipeless or One Pipe Furnaces Section II. (a) When but one duplex grat- ing is used for both warm air and cold air in a so-called pipeless furnace,the area of the cold air intake shall be at least equal to the area of the warm air outlet of the grating. Art. 4, Sec. 4, relative to casings shall not govern when this type of furnace is installed, but the following specification shall be followed: The inner and outer casings of this type of furnace may be made of either black or galvanized iron not lighter than No. 26 U.S. Standard Gauge. A uniform air space shall be maintained at all points between the inner and outer casing. In no case shall the top of the heater be allowed closer than twelve inches(12")to any ceil- ing or joists above the furnace. (b) Where joists are cut to accommodate this furnace, headers shall be put in and braced. (c) Article No. 3 for determining area of (Is) warm air pipe shall not govern in figuring a pipeless furnace. (d) Where one warm air register face is used and separate face or faces for cold air supply are used,then Article No.4,Sections 5,7 and 8 shall apply. ARTICLE NO.5. The following provisions shall be made by the owner or building contractor, in any building wherein a gravity warm air heating system is to be installed. Chimney Provide a chimney for the furnace, constructed in a manner to comply with the following specifications. (a) The chimney must be absolutely smoke tight throughout its entire length,and must extend at least three feet (3') above a flat roof or two feet (2') above the ridges of peak roofs. (b) If built of a single thickness of brick or of cement blocks,it shall be lined through- out its entire length with fire clay flue lining, having not less than three-fourths inch (%") thickness. Flue lining to be laid in mortar and made air tight. (c) The furnace flue must have no other opening for attaching any fireplace,furnace, stove, range,water heater,gas or ventilat- ing connection. The chimney thimble shall be furnished and installed by owner or building contractor, of the size and in the location specified by the Heating Con- tractor. (d) If necessary to offset the flue,it must be done in such a manner as not to reduce the cross sectional area or create a ledge or obstruction, where loose material may lodge. (e) The narrowest internal dimension shall be not less than eight inches (8") and no flue smaller than 8" x 8" rectangular or eight inch(8")diameter round will be con- sidered suitable when hard coal is to be burned,or 8"x 12"rectangular or ten inch (10")round for soft coal or wood. Note 8. /t 13 strongly recommended that nothing leas than 8"s/2"Internal dimensions used in any case. Note 9. It to recommended that the height above the furnace grate be not less than twenty-six feet(26'). Note/0. /1 is strongly recommended that all new chtmne�'be built in.strict accordance with the ordinance recommended Si,i the National Board of Fire Underwriters. Furnace Foundation The furnace foundation must be provided by the Owner or Building Contractor as outlined in Art.4 Sec.2-a. (19) Building (a) Where warm air register boxes,heads, pipes or stacks are to be installed, joists shall be set not less than sixteen inches(16") on centers and shall be butted and not lapped. Studding shall be set directly over and under joists, leaving a space of not less than fourteen inches (14") between studs and joists. Wherever joists are cut, headers must be put in to support joists. (b) All first story single or sub-floors shall be continuous. In all houses having studded exterior walls,these floors shall be extended to the outside sheathing and all spaces be- tween studding shall be closed at the attic line. Note I I. It is strongly recommended that the attic he tightly floored or ceilings insulated to reduce heal losses. (c) All partition walls(or sections of these walls) in which heat stacks to second or third floor rooms are to be installed,shall be of sufficient size to accommodate stacks re- quired to heat said rooms. Outline Page Art. I—Meaning of Terms. 5 Art.2—Certified Measurements 5 Art.3—Formulas 6 Sec. 1-8—Working Rules. 6-10 Sec.9—Furnace Rating Formula. 0 Humidity 0 Second Floor Heating 1 Gas or Oil Fired Furnaces. 1 Art.4—Installation. 1 Sec. I—Location of Furnaces 1 Sec.2—Foundation 1 Sec.3—Setting Furnace 2 Sec.4—Casings 2 a.Portable b.Brick Set Sec.5—Basement Pipes 13 Sec.6—Wall Stacks 14 a.Single b.Double a:} Method of Installation Sec.7—Registers 15 Sec.8—Air Supply to Furnace 15-17 Sec.9—Smoke Pipes 17 Sec. 10—Room Heaters 18 Sec. II—Pipeless Furnaces 18 Art.5—Provisions in Building by Owner or Builder. 19 (20) • . AN-ORDINANCE AN ORDINANCE ADOPTING the ` Standard Cede-for the Installation of Gravity Warm Air Heating Systems in buildings need for human habitation • sand providing penalties for the viola- f ion of.the provisiione of said code. Be it ordained by the Board of OOm. mlesioaere of Salt Leke City,Utah: Sthe.S 1. ThCU the eighth edition ■1'1 g4gyT off 1ub1trattuu Of the SthnOf Gravity.Oode Regulating the �, JJIgVfp04.►►11�l�. 4g 1 tugtSystem ofbuildg.Used Air for Heat- ing Eyabmh in adopted,tppr for and man habitation adopted,W approved and ingiss Ad bytha National ., the Air Heat. Society tyeociation,epti Inc., the ding S- oceere of Heating as VenNational Ae Sol En- 0mShort the ntiac Is of Sheet Metal ContractorsakeCitys he or. "adopted,by Salt Lake u the er-• :alit! Cainin et,rules to dand i regulationse bIC per- ' taml¢gq((warm air heatlnng the tame i- SS. elnbuildins,usedfortihumnhbite AKE 3 of eaid code city; herebydamended by adding to raid article a new section'to 'be known 943 section 3A,which shall, reed ae follow.: 9A.In determining the B.t.u.loss of any structure coming under thin Bede by the use of the constants and s It i0et definitely reecognised(Article 3) • HARRY.',7ALEE apply to the ordinary building When 'the aforesaid rules and constants are ' applied to the individual room and the to o heat tionfof the a slrtu eaeoe g being first duly sworn, deposes and says, that he is the Principal Clerk Sped by each individual room.Where a structure differs from the ordinary residence, tgdrr pester than that lthat where thin ordinarye , of the SALT LAKE DAILY TRIBUNE, a newspaper erslaence or where more than two'air published in changes per hour are required, the ,r foregoing rules shall not be used,,but tshallobel heat determined bytthe etaesneera Salt Lake City, Salt Lake County,State of Utah. method Awing Coefficients of 'heat transfer. Should it'be desired tO con, etruct a building whose wall construc- tion does not come under one of the That the Notice..A11-.-(:IMI:ALT-C.E. city• engineer icatio s set out in this soda,the.. shall determine or shall be assured to his entire satisfaction as W the coefficient of heat transfer for : 1t �„ C IT N such material or such combination of Z C i P'C Ht1 T I materials and-such coefficient Of beat beused shall be used in determining the , tout B.t.u...to be provided for by the furnace.And Article 3 Se further amended by adding to said article a new eectlun to be known as Section 10,which obeli read as'follows,to wit: SEC.10: All warm air heating fur- naces installed within the Loorporata ake limits of the City of Salt Lake and thi cod b rat iomting ithi t.us co e shell by be add of which a copy is hereto attached, was first published in said news- -engineer or his authorized ioDreseata- tive when said'furnaces are.treed.tp burn fuels ordinarily available in the City of Salt Lake;the terml"be- paper in its issue dated the 191:Z1 of till Sag defined for purposes of tine code" as bituminous,coal;Coke,fuel.Oil O¢1O1r neee the er has not been eattieffed d es to the N C V e m be r rating of any warm air hooting fur-- day of , 193 2 nape offered for installation within, r the corporate limits of the City Of Salt Lake or combination of midi furnace and was published in each daily issue of said newspaper, on and stoker,in B,t.u:a at the bonnet, then in that event he eh rate said, furnace according formulato and rule I 19th. est out In Section 9 of the Standard° November Code Regulating the Installation"offor . Gravity Warm Air Heating Systems for - Residences, And said code le further amended by, (.41e insertion 6 umineranli entirely therefrom Article thereafter, the full period of and in lieu thereof Article 3 Abell' read as follows •Article.e. Any structure coming within this code shall be provided With a chlinney Which shall be constructed the last publication thereof conformance in conformance with"A Standard Or- dinance for Chimney Construction" recommended by the National Board Of- Pire Underwriters, third edition, re- being in the issue dated the vieed 1937. The minimum net dimen 19tk1 day of anon of such chimney shell not be lees than la mchee nor!hall the mos.lac- n anal,area be less in square inches 1z oV embe r L than the total B.t.n,loss of the: ,A.D. 19 etruCture divided by 1900. The mini- mum height of chimney shall be such so that when a furnace is metalled the' / height or said chimney will be not lees than 31 feet.above the grate of,said S EI. SECCTION 3. All taped i warm did air heatlhg systems metalled m bWidi La aCltyandallinstallation masod for•human habitatiOn nit- Li sworn to before me this 19th day of •etmetum work Incidental therein shall etrlotiy complq With and conform'W- the provision.of the Standard Warm .Air Heating Code end amendments mb.er ,A.D. 193 2 adopted 1n Section 1,of this °sell-'. nano. • SECTION 3, This cote may be cited and designated aa.the Standard Warm ..Air Heating Code. -. .SECTION 4.-.Any Parton vWlating of She pvrOvisions O.f the Standard Wsm • air Heating Cade shall,mien cornea- Notary Public. �'. in ouon thereof, sume no•t be gggone hundred dollar..($100.00),or by.lmptiednment in the city-jall for a Deriodnot exceed- ing thirty(30)days,or by both ankh', • fine-and Smprieoament. The court may,In impoeidg a fine,enter as part, • of the judgment that,•in default of _payment, yment,of the firle,the defer t" ay be imprisoned in'the city-fan ■period,not exceeding six-months, SECTION 8. In the Opinion of.the Advertising eery to t ie v sot,ri nith'andlesafetyyeootf g fee,$ 'the lnbabitente of Salt Lake City that' this ordinance take effect immediately. SECTION a This ordinance shall. 'I take.effect upon Its first nubllcatione Passepd by the Board of Commiesion- erg of Salt Lake City,Utabo On-the 17th, day of-November,A.D.1893322 - JOHN hf$NICOPP Temporary Chairegan �PH ,MACDONALD Oitf^Recorder, Bail NNop 3�. " -,Ptajllehed November 19llosbfk 1.•,; 1 r , _ r Z I A t' I .0 El7:: = .., ,..ta C.) 'Z 4 4 0 ...=-- ..,. ‘-j