Loading...
047 of 1983 - Amendment of Title 15 Relating to Fire Prevention Codes A ' 0 83-29 -ILMED MICROFILMED SALT LAKE CITY ORDINANCE No. 47 of 1983 (Fire Prevention - Adoption of Uniform Fire Code) AN ORDINANCE AMENDING TITLE 15 OF THE REVISED ORDINANCES OF SALT LAKE CITY , UTAH, 1965 AS AMENDED, RELATING TO FIRE PREVENTION CODES; BY REPEALING SAID TITLE 15 AS IT ADOPTS BY INCORPORATION BY REFERENCE THE SALT LAKE CITY LIFE/FIRE SAFETY CODE, 1977 EDITION, AND BY REENACTING BY INCORPORATION IN LIEU THEREOF, THE UNIFORM FIRE CODE, 1982 EDITION WITH AMENDMENTS AND EXCEPTIONS THERETO. WHEREAS, the Fire Department recommends and the City Council of Salt Lake City, Utah, agrees that for purposes of fire preven- tion, it is desirable to adopt with amendment the provisions of the 1982 Uniform Fire Code in lieu of the City's Life/Fire Safety Code, and provide for its administration; THEREFORE, be it ordained by the City Council of Salt Lake City , Utah: SECTION 1 . That Title 15 of the Revised Ordinances of Salt Lake City, Utah, 1965, as amended, relating to fire prevention, life/fire safety, and the adoption by reference of the Salt Lake City Life/Fire Safety Code, 1977 Edition is hereby REPEALED. SECTION 2. That said Title 15 of the Revised Ordinances of Salt Lake City, Utah, 1965, relating to fire prevention, be, and the same is hereby RE-ENACTED to read as follows : TITLE 15 FIRE PREVENTION Chapters : 1 . Fire Prevention Bureau & General Administration 2. Uniform Fire Code and Amendments 3 . Enforcement and Penalties. Chapter 1 FIRE PREVENTION BUREAU AND ADMINISTRATION Sections: 15-1-1 . Establishment and Duties of the Fire Prevention Bureau. 15-1-2. Definitions. 15-1-3 . Establishment of limits of districts in which storage of flammable or combustible liquids in outside above ground tanks is prohibited. 15-1-4. Establishment of limits or districts in which storage of liquified petroleum gases is to be restricted or prohibited. 15-1-5. Prohibition and Restriction of Storage of Explosives and Blasting Agents. 15-1-6. Administrative Rule Making. Sec. 15-1-1. Establishment and Duties of the Fire Prevention Bureau. (a) There is hereby established a Fire Prevention Bureau of -2- the Fire Department of Salt Lake City , Utah, sometimes referred to as the "Bureau", which shall be under the supervision of the Chief of the Fire Department. Said Chief may delegate administration of the Fire Prevention Bureau and the enforcement of the Uniform Fire Code adopted by this title to one of his subordinates, who for purposes of this title shall be referred to as the "Fire Marshal". Said Fire Marshal shall be the Chief' s duly authorized representative to administer the Bureau and the Uniform Fire Code. (b ) The "Fire Marshal" shall be appointed by the Chief of the Fire Department on the basis of the candidate 's fitness for the position. (c ) The Chief of the Fire Department may detail such members of the Fire Department as Inspectors as shall from time to time be necessary. The Chief of the Fire Department shall recommend to the Mayor the employment of Fire Prevention Specialists, who, when such authorization is made, shall be selected through an examination to determine their fitness for the position. Sec. 15-1-2 . Definitions. ( a) Wherever the words "Board of Appeals" are used in this title, they shall mean the Board of Appeals and Examiners of Salt Lake City described and defined herein in Section 15-2-3. 1 and in Title 5 of the Revised Ordinances of Salt Lake City, Utah, 1965, as amended. -3- (b) Wherever the word "jurisdiction" is used in the Uniform Fire Code, it shall mean Salt Lake City, Utah. (c ) Wherever the words "Chief of the Bureau of Fire Prevention" are used, they shall mean "Fire Marshal" . (d) Wherever the word "Chief" or "Fire Chief" is used , it shall mean the Chief of the Fire Department. (e) Wherever the words "these ordinances" are used, it shall mean the Revised Ordinances of Salt Lake City, Utah, 1965 as amended. ( f) Wherever the words "building code" are used, it shall mean the Uniform Building Code as adopted and amended by Chapter 7 of Title 5 of the Revised Ordinances of Salt Lake City, Utah, 1965 as amended. Sec. 15-1-3 . Establishment of limits of districts in which storage of flammable or combustible liquids in outside above ground tanks is prohibited . The storage of flammable or combustible liquids in outside above ground tanks regulated by Article 79 of the Uniform Fire Code, as adopted in Section 15-2-1 of these ordinances shall be prohibited and unlawful except in those zoning use districts established under Title 51 of these ordinances which specifically authorize such use. Such districts authorizing such storage as a permitted use and their boundaries constitute the limits referred to in Section 79. 501 of the Uniform Fire Code as adopted by this title. Where zoning allows such uses by right, the use shall conform with the technical -4- requirements of said Article 79. Sec. 15-1-4 . Establishment of limits or districts in which storage of liquified petroleum gases is to be restricted or prohibited . The storage of liquified petroleum gases regulated by Article 82 of the Uniform Fire Code, as adopted in Section 15- 2-1 of these ordinances shall be prohibited and unlawful except in those zoning use districts established under Title 51 of these ordinances which specifically authorize such use. Such districts authorizing such storage as a permitted use and their boundaries constitute the limits referred to in Section 82 . 105( a) of the Uniform Fire Code as adopted by this Title. Where zoning allows such uses by right, the use shall conform with the technical requirements of said Article 82. Sec. 15-1-5. Prohibition and restriction of storage of explosives and blasting agents. The storage of explosives and blasting agents is prohibited and unlawful within the jurisdiction as a matter of right. Where the zoning provisions of Title 51 do not preclude such storage, the storage may be permitted by special permit as a conditional use by the Fire Marshal . Approval of such special permits by the Fire Marshal for such storage shall be restricted and controlled based upon geographical , traffic, population and density and other relevant considerations and by the standards set forth in Article 77 and other applicable provisions of said Uniform Fire Code as adopted by this Title. -5- Sec. 15-1-6. Administrative rule making . The Fire Marshal may recommend to the Chief of the Fire Department and the Chief may adopt, subject to review by the Mayor, such rules and regulations for the operation of the Bureau and the administration of the Uniform Fire Code as adopted by this Title as in his/her judgment shall be necessary and appropriate; provided said rules are not in conflict with State law or City ordinance. Three copies of said rules and regulations after approval by the Mayor shall be on file in the offices of the Chief and the Bureau. Chapter 2 UNIFORM FIRE CODE AND AMENDMENTS Sections 15-2-1 . Uniform Fire Code adopted . 15-2-2. Deletions. 15-2-3 . Amendments. 15-2-3. 1 Appeals - Board of Appeals. 15-2-3 . 2 Permits - Acetylene Generator. 15-2-3. 3 Permit Applications and Fees. 15-2-3 . 4 Inspections. 15-2-3.5 Access Roadway - Fire Lanes 15-2-3 .6 Hose Lines for Demolition. 15-2-3.7-3.9 Reserved. 15-2-3. 10 Fireworks. 15-2-3. 11-12 Reserved. -6- 15-2-3 . 13 Adulterated Liquid as Flammables 15-2-3. 14 Maximum Gross Tank Capacity Indoors. 15-2-3 . 15 Diked Areas. 15-2-3. 16-20 Reserved . 15-3-3 . 21 Testing Fire Extinguishing Systems. 15-3-3.22 Life Safety Requirements for Existing Buildings. Sec. 15-2-1 . Uniform Fire Code adopted. That certain code and standards known as the Uniform Fire Code, 1982 edition, including Appendix Chapters 1-A, I-B, III-A, III-C , and V-A and the Uniform Fire Code Standards, 1982 edition, as promulgated and published by the Western Fire Chief 's Association and the International Conference of Building Officials are hereby adopted by reference by Salt Lake City as the ordinances, rules and regulations of said City, subject to deletions, amendments and exceptions thereto set out in this Title. Three copies of said code and standards have been and shall be on file for public use and examination in the office of the Salt Lake City Recorder. Said code and standards prescribe regulations and procedures to govern or eliminate conditions which can be hazardous to life and property from fire and explosion. They provide for the issuance of permits, collection of fees therefor, and penalties for violations. Hereafter all references in these ordinances to the Uniform Fire Code and/or said Standards shall refer to the 1982 editions thereof. Sec. 15-2-2 . Deletions. Specifically deleted from the -7- Uniform Fire Code adopted above are Appendix Chapters II-A, II-B , II-C, II-D, III-B, IV-A,and VI-A-D, which have no effect in this jurisdiction. Sec. 15-2-3 . Amendments. The following provisions of the Uniform Fire Code be, and the same are hereby listed and are amended to read as set forth hereinafter. Sec. 15-2-3. 1 Appeals - Board of Appeals (§2. 302 ) Sec. 15-2-3 . 2 Permits - Acetylene Generator (§4. 101 ) Sec. 15-2-3.3 Permit Applications and Fees ( 94. 103 ) Sec. 15-2-3 . 4 Inspections ( §4. 104 ) Sec. 15-2-3. 5 Access Roadway - Fire Lanes (§10.207) Sec. 15-2-3 .6 Hose Lines for Demolition (§10 . 316 ) Sec. 15-2-3 .7-3 .9 Reserved. Sec. 15-2-3 . 10 Fireworks ( §78. 102, 103 ) Sec. 15-2-3. 11-12 Reserved. Sec. 15-2-3 . 13 Adulterated Liquid as Flammables (§79. 115 ) Sec. 15-2-3. 14 Maximum Gross Tank Capacity Indoors (§79. 301 ) Sec. 15-2-3. 15 Diked Areas ( §79.508c) Sec. 15-2-3 . 16-20 Reserved Sec. 15-2-3. 21 Testing Fire Extinguishing Systems (App. III-A) Sec. 15-2-3.22 Life Safety Requirements for Existing Buildings (App. 1-A) . -8- Sec. 15-2-3 . 1 Appeals - Board of Appeals. Section 2. 302 of said Uniform Fire Code relating to the Board of Appeals be, and the same is hereby AMENDED to read as follows : Sec. 2.302 Board of Appeals. ( a) Administrative appeal . Whenever the Chief of the Fire Department or the Fire Marshal disapproves an application or refuses to grant a permit or approve plans based upon the Uniform Fire Code, or when it is claimed that the provisions of said Code do not apply or that the true intent and meaning of said Code have been misconstrued or wrongly interpreted, the applicant may appeal said administrative decision to the Board of Appeals and Examiners as established under Title 5 of these ordinances. Said appeal must be filed with the Board within 30 days of the date of the controverted decision. Said appeal shall be heard before such five person Board which shall be enlarged by including as a voting member for such appeals, the Chief of the Fire Department or his representative. The Board 's decision and the related findings shall be reduced to writing and submitted to the Chief with copies to the applicant and Building Official. ( b) Equivalent alternatives. Said Board, enlarged by the membership of the Chief or his representative may also determine the suitability of alternate materials and type of construction; provided, the alternate materials, methods of work performed or operation provides for the purpose -9- intended at least the equivalency of the Code requirement in quality, strength, effectiveness, fire resistance, durability and safety. The Board has no power to waive requirements where equivalency is not otherwise achieved. (c) Recommendations. The Board may recommend new legislation to the Mayor and new regulations to the Chief as it deems appropriate. (d ) Judicial review. Decisions of the enlarged Board of Appeals on matters relating to this Uniform Fire Code shall be final unless appealed by petition for judicial review filed timely (within thirty days from the date of the decision) with a court of competent jurisdiction as provided in Section 5-3-4 of these ordinances. Sec. 15-2-3. 2 Permits for acetylene generators. Section 4. 101 of the Uniform Fire Code, relating to required permits, be and the same is hereby amended by ADDING thereto a new permit which shall read as follows: Sec. 4 . 101 . 1 . * * * 47. Acetylene generator. To operate an acetylene generator having a carbide capacity exceeding five ( 5 ) pounds. See Article 49. Sec. 15-2-3 .3 Permit application and fees. Section 4. 103 of the Uniform Fire Code, relating to permit applications be, and -10- the same is hereby AMENDED, to read as follows : Sec. 4. 103 Permit application and fees. ( a) All applications for a permit required by the Uniform Fire Code, shall be made to the Fire Prevention Bureau in such form and detail as the Bureau shall prescribe. (b) Each application for a permit shall be accompanied by such plans, specifications and drawings for the evaluation of the application as may be required by the bureau. (c ) Each application for a permit shall be submitted to the bureau concurrently with the application fee designated by administrative regulation for the applicable permit, certificate or inspection. Said fee is non- refundable and no permit will be issued without proof of payment of said fees. Sec. 15-2-3 . 4 Inspections. Section 4. 104 of the Uniform Fire Code, relating to permit inspections, be and the same is hereby AMENDED to read as follows : Sec . 4. 104 Inspections. Before a permit may be issued, the Chief or his authorized representative may elect to inspect or test or cause to be inspected or tested the receptacles, vehicles, buildings, devices, premises, storage spaces, areas or any other aspects of the operation or business to assure that the use and activities for which the permit is to be issued comply with the provisions and intent -11- of this Code. In instances where laws or regulations are enforceable by departments other than the Fire Department, joint approval may be required to be obtained from all departments concerned before such permit will be issued. Sec. 15-2-3 . 5 Access roadways. Section 10 .207 of the Uniform Fire Code, relating to access roadways for fire apparatus be, and the same is hereby amended by ADDING new subsection (g ) relating to fire lanes, which shall read as follows : Sec. 10. 207 ( a) Required construction . . . (g) Fire lanes. It shall be the duty and power of the Chief to designate, personally or through the Fire Marshal , fire lanes, where in their judgment the geographical , traffic, population, density or any other relevant factors make such a designation desirable to protect life or property from fire and explosion hazards. They shall be established and designed to enable fire department personnel and equipment to have unimpaired , unobstructed and ready access to the subject premises for the purpose of fire fighting , rescue or control. Said fire lanes may be designated on any premises, public or private and such power of designation shall include, but shall not be limited to hospitals, schools, churches, theatres, restaurants, apartments and hotels, shopping centers and malls. (1 ) To establish a fire lane, the Chief or the Fire Marshal shall give written notice to the person, -1 2- firm or corporation in possession or control of the subject premises, setting forth: ( a) the designation of the fire lane; (b) a general description of its location and necessary width; (c ) the signs, markings or warnings required to physically establish said fire lane and to give notice to others of its existence and location; (d) the time within which said person shall comply. ( 2 ) It shall be the sole responsibility of the person, firm, or corporation in possession or control of the subject premises to provide and maintain any required markings, warnings, or signs after a fire lane has been established as provided above. A fire lane established and created pursuant to this Code shall be kept open and unobstructed at all times. Any person who shall stop, park, stand or in any other way cause or allow a designated and marked fire lane to be blocked or obstructed shall be guilty of a misdemeanor. Sec . 15-2-3 .6 Hose lines for demolitions. Article 10 of the Uniform Fire Code, be and the same is hereby amended by ADDING new section 10 . 316 relating to a requirement of hose lines for the demolition of buildings, which shall read as follows : Sec. 10 . 316 Required hose lines when building -1 3- demolished . Where a building with more than four thousand square feet (4000 square feet) of ground floor area or more than two stories in height is being demolished , charged hose lines at least one and one-half inches (1 1/2" ) in diameter shall be laid to protect combustibles. Also, such hose lines shall be laid during the demolition of any building where the hazard to adjacent or adjoining property warrants. Sections 15-2-3.7 to 3.9 Reserved. Sec . 15-2-3 . 10 Fireworks. Sections 78. 102 and 103 of the Uniform Fire Code, relating to fireworks be, and the same are hereby AMENDED to read as follows : Sec. 78. 102 (a) Manufacturing, storage permit. It is unlawful to manufacture or store fireworks within the limits of the city by any person or entity without first obtaining a permit from the Fire Marshal for such purpose and complying with state and local law. This provision shall not be construed as prohibiting the storage of fireworks for a display for which a permit has been granted under the provisions of public display under (b) below. (b) Public display permit. (1) It is unlawful to conduct any public display of fireworks without obtaining a special permit therefore and fully complying with the provisions of this chapter and these ordinances. The Mayor upon written application, approval from the Fire Marshal and the posting of required insurance may grant permit for -1 4- public display of fireworks by responsible groups as determined by the Mayor. No permit granted hereunder shall be transferable. ( 2 ) Application for permit. The application for a permit to operate a public display of fireworks shall be made in writing at least 10 days in advance of the date of the display. It shall be signed by the applicant and shall contain the following information: ( i ) The name of the organization or persons sponsoring the display, together with the name, ages and qualifications of persons actually in charge of the firing of the display. ( ii ) The date and time of the day at which the display is to be held. ( iii ) The exact location planned for the display. ( iv) The number and kinds of fireworks to be discharged. (v) The manner and place of storage of fireworks prior to the display. ( 3 ) Insurance required. No person or entity shall be issued a permit for the public display of fireworks unless he/she shall have insurance in the minimum sum of $100,000/300,000 liability naming Salt Lake City Corporation as an additional insured. A -15- certificate of insurance showing proof of the required coverage shall be on file with the City Recorder 's office prior to final permission being granted by the Mayor and issued by the Chief pursuant to this article. (c ) After a permit for the public display of fireworks has been granted, sales, possession, use and distribution of fireworks for such display shall be lawful for that purpose only. Sec. 78. 103 Requirements for display. ( a) Nonhazardous manner. After a permit for public display of fireworks has been obtained , such display shall be of a character, and so located, discharged or fired that it will not create a hazard to property or endanger any person, and must comply with the technical standards below. ( b) Firing distance. The actual point at which the fireworks are to be fired shall be at least: two hundred feet ( 200 ' ) from the nearest permanent building , public highway or railroad, and fifty feet (501 ) from the nearest above ground telegraph, telephone or electric power pole or line, tree or other overhead obstruction. (c) Minimum spectator distance. Spectators shall be restrained behind the lines of at least one hundred fifty feet ( 150 ' ) from the point at which the fireworks are discharged. Only persons in active charge of the display shall be allowed inside said line. -16- (d ) Vertical firing required . All fireworks that fire a projectile shall be so set up that the projectile will go into the air as nearly as possible in a vertical direction. (e ) Maximum wind velocity. No fireworks display shall be held during any wind storm in which the wind reaches a velocity of thirty (30 ) miles or more per hour. ( f) Fire extinguishers. Fire extinguishers shall be provided as required by the Fire Marshal . Sec. 78. 104 Disposal of unfired fireworks. * * * Section 15-2-3 . 11-12 Reserved. Section 15-2-3. 13 Adulterated liquids as flammable. Article 79 of the Uniform Fire Code, relating to flammable and combustible liquids be, and the same is hereby amended by ADDING thereto a new Section 79-115 relating to adulterated liquids which shall read as follows: Sec. 79. 115 Adulterated liquid as flammable. Any manufactured liquid or fluid commodity, such as paint, varnish, dryer, cleaning solution or polishing liquid which contains flammable or combustible liquids shall be considered a flammable or combustible liquid and shall be classified according to flash point and/or boiling point as provided in this article. Also, any combination, compounding or mixture of flammable or combustible liquids or nonflammable liquids or substances shall be classified -17- according to the most volatile or dangerous liquid or substance included. Section 15-2-3 .14 Maximum gross tank capacity indoors . Section 79.301 of the Uniform Fire Code, relating to indoor stationary tank storage, be, and the same is hereby amended by ADDING thereto new subparagraph ( f) which reads as follows : Sec. 79. 301 ( e) Testing . . . * * * ( f) Maximum gross tank capacity. In buildings of nonrated construction, the nominal gross capacity of tanks shall not exceed ten thousand ( 10,000) gallons. In fire- resistive buildings the nominal gross capacity of the tanks shall not exceed fifteen thousand ( 15,000) gallons. In any building, if in a fire-resistive or detached room cut off vertically and horizontally in an approved manner from other floors of the main building, the nominal gross capacity of tanks shall not exceed fifty thousand ( 50,000) gallons, with an individual tank capacity not exceeding twenty-five thousand ( 25,000) gallons. Sec. 15-2-3 . 15 Diked areas. That the first introductory paragraph of Section 79. 508 (c) of the Uniform Fire Code, relating to diked areas of drainage tank areas, be, and the same hereby is AMENDED to read as follows: Sec. 79. 508(c) Diked areas. Where protection of adjacent tanks, adjoining property or waterways is accomplished by retaining the liquid around the tank by -18- A means of a diked area, such dikes shall be at least six inches higher than necessary to retain the volumetric capacities detailed below in order to provide for adequate retention of fire-fighting foam on the surface of the stored liquid . Such diked areas shall also comply with the following: ( 1 ) ( 7 ) Sections 15-2-3 . 16 - 20. Reserved. Sec. 15-2-3. 21 Testing fire extinguishing systems. That Appendix III-A of the Uniform Fire Code, relating to testing of fire extinguishing systems be, and the same is hereby amended by AMENDING Section l( a) and ADDING on new Section 2 (f) which respectively shall read as follows: Appendix III-A 1. Testing (a) Except where otherwise required below, tests of systems or devices herein regulated shall be conducted at least every five years. Tests at shorter intervals may be required when an inspection by the fire department indicates that there is reason to believe that the system or device might fail to operate properly in an emergency. (b) -19- (g) 2. Test procedures for automatic sprinkler systems. (a) ( f) Testing standards. Automatic sprinkler systems shall be tested in accordance with NFPA 13-A, "Inspection, Testing and Maintenance of Sprinkler Systems" , published by the National Fire Protection Association, being particularly the 1981 edition thereof. The required testing, inspection and maintenance intervals shall be those summarized in NFPA 13-A Table 7-3 , except that the main-drain or test-pipe- valve flow tests referred to in paragraph (b) above and in NFPA 13-A section 2-6. 1 shall be conducted at least annually. Where NFPA 13-A, 1981 edition conflicts with any part of Appendix III-A of this code, NFPA 13-A, 1981 edition shall apply. Section 15-2-3 . 22 Life safety requirements for existing buildings. That Appendix Chapter I-A of the Uniform Fire Code, 1982 edition relating to regulations applicable to existing buildings, be, and the same is hereby AMENDED to read as follows: Appendix I-A Life Safety Requirements to Existing Buildings 1. General Provisions . ( a) Purpose. The purpose of this appendix is to provide a reasonable degree of safety to persons occupying existing buildings that do not conform -20- with the minimum requirements of this code or the building code by providing for alterations to such existing buildings. (b) Scope. This chapter shall apply to all existing nonconforming buildings. EXCEPTION: Group R Division 3 or Group M Occupancies. (c ) Implementation dates. Within 18 months after the effective date of this appendix , plans for compliance shall be submitted and approved, and within 18 months thereafter the work shall be completed or the building shall be vacated until made to conform. EXCEPTION: Existing nonconforming Group R, Division 1 Occupancies shall be made to conform to the requirements of this appendix immediately or shall be vacated until made to conform. However Group R Division 1 Occupancies less than 3 stories in height shall comply with section 7 below concerning smoke detectors within 18 months of the effective date of this ordinance. (d ) Minimum not maximum standards. Requirements of this Appendix are deemed minimum requirements and if the Building Official or Fire Chief determines that the building in question is otherwise unsafe, and does not provide the protection and safety contemplated herein, he may invoke whatever applicable law he deems appropriate to effectuate -21- the intended purposes of this section. (e ) Equivalent alternative by Board of Appeals. No alternate equivalent method or exception to the fire protection and safety requirements of this appendix may be used and authorized unless the Board of Appeals, including as a voting member for this purpose the Chief of the fire department, finds that such alternate method provides protection and safety equivalent to that required herein. The Chief of the fire department may modify any of the provisions of this appendix in conformance with section 2 .301 of this code. 2 . Exits. ( a) Number of exits. Every floor, apartment, sleeping room or usable portion thereof above the first story used for human occupancy shall have access to at least two separate exits, one of which may be an exterior fire escape complying with subsection 2 (c) of this appendix . EXCEPTION: In all occupancies, second stories with an occupant load of 10 or less may have one exit. (b) Stair and stairway construction. ( 1 ) Rise and run. All required stairs shall have a minimum run of 9 inches and a maximum rise of 8 inches and shall have a minimum width of 30 inches, exclusive of handrails. Every stairway shall have at least one handrail . A landing having a minimum 30 inch run in the direction of travel shall be provided at -2 2- each point of access to the stairway. EXCEPTION: Fire escapes as provided for in this appendix. ( 2 ) Interior stairways. Interior stairways shall be enclosed by a minimum of one-hour fire-resistive construction. Where existing partitions form part of a stair enclosure, wood lath and plaster or 1/2 inch gypsum wallboard in good condition will be acceptable in lieu of one-hour fire-resistive construction. Each opening into such stairway shall be protected by an assembly equivalent to a solid wood door not less than 1 and 3/4 inches thick which shall be maintained self- closing or be automatic-closing by smoke detection. When glass is used in the doors, it must conform to the requirements of Sections 4306 (g) and ( i ) of the Building Code. All other openings shall be fire protected in an approved manner. Existing fusible link type automatic door closing devices may be permitted if the fusible link rating does not exceed 135 degrees farenheit. EXCEPTIONS: ( i) In other than Group I Occupancies, an enclosure will not be required for stairs serving only one adjacent floor. ( ii ) Stairways need not be enclosed in a continuous vertical shaft if each story is -2 3- separated from other stories by one hour fire resistive construction. Where existing construction forms part of a separation, wood lath and plaster or 1/2 inch gypsum wallboard in good condition will be acceptable in lieu of one hour fire resistive construction. ( iii ) Stairways need not be enclosed nor stories separated if an approved automatic sprinkler system is provided for all corridors, stairs, exits and other common areas. ( iv) For Group R, Division 1 Occupancies, when it is determined by the Fire Marshal with approval of the Board of Appeals to be totally impractical to enclose the stairways as contemplated by this Section, the Chief may approve that not more than two apartment doors on each floor be within each stairway enclosure. Such approval can be considered, provided: that these doors are 1 & 3/4 inches thick solid core self-closing doors or equivalent; and further provided, that such enclosure wall be built as close to these doors as possible but in no case more than 5 feet away from these doors. Where this alternative is permitted, a second door or other approved secondary means of egress from each apartment so affected shall be -24- provided on the hall side of the enclosure. (3 ) Exterior stairs. Exterior stairs shall be noncombustible or of wood of not less than two inch nominal thickness with solid treads and risers. (c ) Fire escapes. (1 ) Existing fire escapes which in the opinion of the Chief comply with the intent of this section may be used as one of the required exits. The location and anchorage of fire escapes shall be of approved design and construction. ( 2 ) Fire escapes shall comply with the following : ( i ) Access from a corridor shall not be through an intervening room. ( ii ) Egress from the building shall be by a clear opening having a minimum dimension of not less than 29 inches. Such openings shall be openable from the inside without the use of a key or special knowledge or effort. The sill of an opening giving access shall be not more than 30 inches above the floor of the building or balcony. ( iii ) Fire escape stairways and balconies shall support the dead load plus a live load of not less than 100 pounds per square foot and shall be provided with a top and intermediate handrail on each side. The pitch of the stairway shall not -25- exceed 60 degrees with a minimum width of 18 inches. Treads shall be not less than four inches in width and the rise between treads shall not exceed ten inches. All stair and balcony railings shall support not less than 50 pounds per lineal foot of railing. ( iv) Balconies shall be not less than 44 inches in width with no floor opening other than the stairway opening greater than 5/8-inch in width. Stairway openings in such balconies shall be not less than 22 inches by 44 inches. The balustrade of each balcony shall be not less than 36 inches high with not more than nine inches between balusters. The lowest balcony shall be not more than 18 feet from the ground. (v) Fire escapes shall extend to the ground or be provided with counter-balanced stairs reaching to the ground. (vi ) Fire escapes shall extend to the roof or provide an approved gooseneck ladder between the top floor landing and the roof_ when serving buildings four or more stories in height having roofs with less than 4 :12 slope. (3 ) Ladder. Subject to the approval of the Chief, an approved exit ladder device may be used in -26- lieu of a fire escape when the construction features or location of the building on the property make the installation of a fire escape impracticable. Any exit ladder device shall also conform with U.B.C. Standard No. 33-3 , 1982 edition, and the following : ( i ) Serves an occupant load of ten or less or a single dwelling unit or guest room. ( ii ) The building does not exceed three stories in height. ( iii) The access is adjacent to an opening as specified for emergency egress or rescue, or from a balcony. ( iv) Shall not pass in front of any building opening below the unit being served. (v) Any activating or actuating device for the ladder is accessible only from the opening or balcony served. (vi ) So installed that it will not cause a person using it to be within six feet of exposed electrical wiring or power lines. Fire escape ladders shall be designed and connected to the building to withstand a horizontal force of 100 pounds per lineal foot; each rung shall support a concentrated load of 500 pounds placed anywhere on the rung. All ladders shall be at least 15 inches wide, -27- located within 12 inches of the building and shall be placed flatwise relative to the face of the building. Ladder rungs shall be 3/4 inch in diameter and shall be located 12 inches on center. Openings for roof access ladders through cornices and similar projections shall have minimum dimensions of 30 inches by 33 inches. ( 4 ) Fire escapes and exit ladder devices shall be kept clear and unobstructed at all times and maintained in good working order. Neither fire escapes nor exit ladder devices shall take the place of stairways required by the codes under which the building was constructed. (d ) Corridors. Corridors of Groups A, B, E, I , H and R, Division 1 Occupancies serving as an exit for an occupant load of 30 or more, and corridors of Group R, Division 1 Occupancies more than two stories in height shall have walls and ceilings of not less than one hour fire resistive construction as required by the building code. Existing walls surfaced with wood lath and plaster or 1/2 inch gypsum wall board in good condition or openings with fixed wired glass set in steel frames are permitted for corridor walls and ceilings and occupancy separations when approved. Doors opening into such corridors shall be protected by 20 minute fire assemblies or solid wood doors not less than 1 & 3/4 inches thick. Where the existing frame will not accommodate -28- the 1 & 3/4 inches thick door, a 1 & 3/8 inches thick solid bonded wood core door or equivalent insulated steel door shall be permitted. Doors shall be self closing or automatic-closing by smoke detection. When glass is used in the doors , it must conform to the requirements of sections 4306 (g) and ( i) of the building code. EXCEPTIONS: Existing corridor walls , ceilings and opening protection not in compliance with the above may be continued , provided an approved automatic sprinkler system is provided for all corridors, stairs, exits and other common areas. Such sprinkler system may be supplied from the domestic water system if it is of adequate volume and pressure. (e ) Doors and openings. Exit doors shall meet the requirements of Section 3304 (b) , (c) and (d) of the building code. Doors shall not reduce the required width of stairways more than six inches when open. Transoms and openings other than doors from corridors to rooms shall comply with Section 3305 (h) of the building code or shall be fixed closed and covered with a minimum of 3/4 inch plywood or 1/2 inch gypsum wall board or equivalent material on the room side. ( f) Exit and fire escape signs. Exit signs shall be provided as required by the Building Code. EXCEPTION: The use of existing exit signs may be -29- continued when approved by the Chief. 3. Enclosure of vertical openings. Elevator shafts, ducts, and other vertical openings shall be enclosed as required for stairways in subsection 2 (b) above or wired glass set in metal frames. Doors shall be noncombustible, or as regulated in subsection 2 (b) above. 4 . Occupancy separations . Occupancy separations shall be provided as specified in Section 503 of the Building Code. Lobbies and public dining rooms not including cocktail lounges shall not require a separation if the kitchen is so separated from the dining room. In Group R, Division 1 Occupancies, any room containing a boiler or central heating plant shall be separated from the rest of the building by not less than a one-hour fire-resistive occupancy separation. When approved by the Chief, existing wood lath and plaster or 1/2 inch gypsum wall board in good condition may be acceptable where one-hour occupancy separations are required. EXCEPTION: A separation shall not be required for such room with equipment serving only one dwelling unit in a Group R, Division 1 Occupancy. 5. Basement access or sprinkler protection. An approved automatic sprinkler system shall be provided in basements or stories exceeding 1500 square feet in _gross area and not having a minimum of 20 square feet of opening -30- entirely above the adjoining ground level in each 50 lineal feet or fraction thereof of exterior wall on at least one side of the building . Openings shall have a minimum clear dimension of 30 inches. If any portion of a basement is located more than 75 feet from required openings, the basement shall be provided with an approved automatic sprinkler system throughout. 6. Standpipes. Any buildings over four stories in height shall be provided with an approved Class I or Class III standpipe system. 7. Smoke Detectors . ( a) Required in dwelling units and guest rooms. Every dwelling unit, and every guest room in a hotel or lodging house used for sleeping purposes shall. be provided with approved smoke detectors. In dwelling units, such detectors shall be mounted on the ceiling or wall at a point centrally located in the corridor or area giving access to rooms used for sleeping purposes. In efficiency dwelling units, hotel sleeping rooms and in hotel suites, the detector shall be centrally located on the ceiling of the main room or hotel sleeping room. Where sleeping rooms are on an upper level , the detector shall be placed at the center of the ceiling directly above the stairway. Wall mounted detectors shall be mounted as near to the ceiling as possible but no detector shall be mounted within 12 inches of any corner formed by the meeting of -31- walls, ceilings, beams or other structures. Care shall be exercised to insure that the installation and maintenance will not interfere with the operating characteristics of the detector. When actuated,the detector shall provide an alarm in the dwelling unit or guest room. (b) Corridor. In lieu of the smoke detectors in every dwelling unit, the smoke detectors meeting the requirements above may be installed in the corridors and common areas spaced a maximum of 30 feet apart. Chapter III ENFORCEMENT, PENALTIES Sections 15-3-1 . Withholding , suspension, revocation of permits. 15-3-2. Mandatory and prohibitionary nature of chapter. Violations, fines, penalties. 15-3-3. Severability. 15-3-4 . Repeal of conflicting ordinances. Sec. 15-3-1. Withholding, suspension, revocation of permits. The Chief may, in writing , withhold issuance, suspend or revoke permits under his/her respective authority subject to this title, whenever good cause is shown to question the propriety of issuance, or it appears the permit is issued in error or on the basis of incorrect information supplied, or in violation of any ordinance or regulation or any provisions of these ordinances. -3 2- Sec. 15-3-2 . Mandatory and prohibitionary nature of chapter. Violations, fines, penalties. (a) It shall be unlawful for any person, firm or corporation to violate any of the provisions of this Code or Standards hereby adopted by this title or to fail to comply therewith; or to violate or fail to comply with any order made thereunder; or to build in violation of any detailed statement of specifications or plans submitted and approved thereunder, or any certificate or permit issued thereunder, and from which no appeal has been taken; or to fail to comply with such an order as affirmed or modified by the Board of Appeals, including as a voting member for this purpose the Chief of the Fire Department, or by a court of competent jurisdiction, within the time fixed herein and shall be guilty of a misdemeanor for each and every such violation and noncompliance. No permits shall be issued to any applicant during the time: he/she fails to correct defective work or noncomplying work; or, a violation continues to exist. The conviction for any violation shall not excuse the violation or permit it to continue; and all such persons shall be required to correct or remedy such violations or defects within a reasonable time. The maintenance of prohibited conditions shall constitute a separate offense. (b) Fines and penalties. Upon conviction for such violations of this title, such party,if a person, shall be punishable by a fine of not more than $299 and/or imprisonment of -33- not more than six ( 6 ) months. If such party is a corporation, association, partnership or governmental instrumentality, such party may be subject to a fine not exceeding $2 ,000 and/or imprisonment of not more than six ( 6 ) months. (c) Abatement. The application of the above penalty shall not be held to prevent the enforced removal of prohibited conditions. Sec. 15-3-3 . Severability. If any section, subsection, sentence, clause or phrase of this ordinance is for any reason held to be invalid or unconstitutional by the decision of any court of competent jurisdiction, such decision shall not affect the validity of the remaining portions of this ordinance. The City Council hereby declares that it would have passed this ordinance and each section, subsection, sentence, clause and phrase hereof, irrespective of the fact that any one or more of the sections, subsections, sentences, clauses or phrases hereof be declared invalid or unconstitutional. Sec. 51-3-4 . Repeal of conflicting ordinances. All former ordinances or parts thereof conflicting or inconsistent with the provisions of this ordinance or of the Code or Standards hereby adopted are hereby repealed. SECTION 3. This ordinance shall take effect upon the date of its first publication. -34- Passed by the City Council of Salt Lake City, Utah, this 12th day of July , 1983. CHKIRMAN ATTEST: Y� G CITY RECO D'ER Transmitted to the Mayor on July 18, 1983 Mayor's action July 18, 1983 M OR ATTEST: cc75 ' Rev. 6/20/83 (SEAL) BILL 47 of 1983 Published synopsis: July 29, 1983 -3 5- Affidavit of Publication r STATE OF UTAH, s s. County of Salt Lake Chex.l..Gierloff ................................................................... SALT LAKE, OF ORDI- Being first duly sworn, deposes and says that he is legal (Fire PNp 1-Adoption of advertising clerk of the DESERET NEWS, a daily The seltmake criCodco�,'ncl�at (except Sunday) newspaper printed in the English its Julyamended 12,,tle 1"3 meeting language with general circulation in Utah, and Ord of �t Cake city, published in Salt Lake City, Salt Lake County, in the Utah,1965 as amended,relating to Fire Prevention Codes; by State Of Utah. repeafing said Title 15 as it adopts by Incorporation by ref- erence Via SALT LAKE CITY LIFE/FIRE SAFETY CODE, 'Itn 6DITiON,and reenacting That the legal notice of which a copy is attache hereto byy�incorporation in lieu thereof, ; THE UNIFORM FIRE CODE, ' IM EDITi!ON with amend- ments and exceptionsthereto. Ordinance No. 47 of 1983 - Fire Prevention Said code as amended In Title ....... ................................................ 15 establishes regulations safe gUarQing'life and property from hazardsjof.fire and:expldfslon; c a arising from storage',.han�OdFFiing• adOpta On 01,U, ,fo, ���.e...�S?c3e..................................... And'ose ot•hazardous substanc- ................ A�•• woos, materials and gevlces and -from cafdltions hazardous W life or graperty in the design, use or occupacv of buildings I ............................................................................................................... br properiV. Sa(d Title.also provides: (1) for' ini3tration by the Fire Prevention Bureau; (2) for ............• permit fee schedules to be adopted by regulation; (3) for enforcement and penalty prove- lions. Acopy of the adopted:ordi- ............................................................................................................... nandx In its entirety is avail- able In the Office of the City Recorder, Room 311, City and County Building, between 8:00 was published in said newspaper on......................................... ►Trough Friday,f►� Monday- oo This ordinance shall,be effec- U� ...2, ,,,,,� {..y.,�..................... five upon firStpublication. a. . Pubfished:511Y 29,1983 C-77 Legal A rtising erk Subscribed and sworn to before me this ...............................em............................................ day of ..............Augu.st....................................A.D. 19..83... .................. 1 Notary Public My Commission Expires Juir 23, 1986 ................................................................ Ki }!S ADM 35A